Verify the module chassis size – Rockwell Automation 1738-AENTR, Series B POINT I/O and ArmorPOINT I/O Dual Port EtherNet/IP Adapters User Manual User Manual

Page 79

Advertising
background image

Rockwell Automation Publication 1734-UM017B-EN-P - October 2013

71

Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software Chapter 5

Notice that the 1756-ENBT Bridge is now online.

If yellow triangles are present, see the following section.

Verify the Module
Chassis Size

You have now built the I/O tree and the RSLogix 5000 software uses the chassis
size from the General tab of the adapter for the rack-optimized I/O connection.
Now you need to configure this new chassis size value into the adapter non-
volatile memory. This procedure synchronizes the chassis size value from the
RSLogix 5000 software into the adapter hardware. You must be online to
perform this procedure.

1. Verify that the RSLogix 5000 software is online.
2. Right-click the name of the adapter under I/O Configuration in the

Project dialog.

3. Select Properties.
4. Click the Connection tab.

The Module Fault error code displays at the bottom of the
Connection tab.

5. Click the Chassis Size tab.