Chapter 5 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software

4. From the New Module dialog, complete the following:

Enter a value for Name.

Enter a value for Slot.

5. Select Change...

The Module Definition dialog displays.

6. Select Data as the Connection and click OK.

This configures the controller to make a Direct I/O Connection to the
module.

7. From the New Module dialog, select the Connection tab to set the RPI

value. RPI is selectable since it is a direct connection.

8. From the New Module dialog, enter 50 for the Requested Packet Interval

(RPI).

9. Keep the following unchecked.

a. Inhibit Module

IMPORTANT

To avoid overloading the I/O adapter, we recommend that the RPI be
no less than 10 ms for rack connections and 50 ms for direct
connections.