Rockwell Automation 1738-AENTR, Series B POINT I/O and ArmorPOINT I/O Dual Port EtherNet/IP Adapters User Manual User Manual
Page 70
62
Rockwell Automation Publication 1734-UM017B-EN-P - October 2013
Chapter 5 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software
6. Enter or select values for Series, Revision, Electronic Keying, Connection,
and Chassis Size, noting that we used the following values:
Connection choices include:
•
None – the adapter makes a direct connection to each of the modules
referenced by the data.
•
Rack optimization– digital I/O data is collected into a rack image. This
does not include analog or specialty I/O modules.
•
Listen only - rack optimization– read or verify data only, but does not
control the modules. When you have multiple controllers - one controller
is used to control and the other controllers are used to monitor.
7. Because we are making a mixed connection (both a direct connection and
rack-optimized connection), choose Rack Optimization as the
Connection for the 1738-AENT adapter and click OK.
A dialog box opens.
8. Click Yes.
Series
B
Connection
Rack Optimization
Chassis Size
5
Electronic Keying
Compatible Module
Revision
4.3
IMPORTANT
The chassis size value equals 1 for the adapter plus the number of I/O
modules installed (physically present on the I/O backplane).