Rockwell Automation Publication 1734-UM017B-EN-P - October 2013

Chapter 5 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software

6. Enter or select values for Series, Revision, Electronic Keying, Connection,

and Chassis Size, noting that we used the following values:

Connection choices include:

None – the adapter makes a direct connection to each of the modules
referenced by the data.

Rack optimization– digital I/O data is collected into a rack image. This
does not include analog or specialty I/O modules.

Listen only - rack optimization– read or verify data only, but does not
control the modules. When you have multiple controllers - one controller
is used to control and the other controllers are used to monitor.

7. Because we are making a mixed connection (both a direct connection and

rack-optimized connection), choose Rack Optimization as the
Connection for the 1738-AENT adapter and click OK.

A dialog box opens.

8. Click Yes.

Series

B

Connection

Rack Optimization

Chassis Size

5

Electronic Keying

Compatible Module

Revision

4.3

IMPORTANT

The chassis size value equals 1 for the adapter plus the number of I/O
modules installed (physically present on the I/O backplane).