Individual parameters can be adjusted by the user.

• Press the MANUAL button. ①
• It will display like the diagram to the right.
• Press INITIALIZE first. ②

• Pressing MEASURE BODE carries out the frequency

response measurement, and displays the waveforms.

• By changing the GAIN [dB] value and measuring the

frequency response, the Gain waveform will move up

and down according to the GAIN value.

• By changing the Q value and measuring the

frequency response, the Phase waveform will move

up and down according to the Q value.

• Adjust so that the gray waveform and black waveform

overlap.

• Pressing MEASURE STEP carries out the step

response measurement, and displays the step

waveforms.

• Change the FFGain and Overshoot values, measure

the step response, and adjust so that the gray

waveform and black waveform overlap.

• Starting with HiSpeed Serial makes it possible to

adjust individual parameters while operating

high-speed serial communications.

• Save the tuning results to EEPROM. Refer to 9.4. Writing Parameters into ROM.