Table 3-14. Regulate Industry Menu Parameters

Parameter

Choices

Description

SNPSHT

DISPLY
SCALE

Display or scale weight source.

ZTARE

NO
YES

Remove tare on ZERO.

KTARE

YES
NO

Always allow keyed tare.

MTARE

REPLAC
REMOVE
NOTHIN

Multiple tare action.

NTARE

NO
YES

Allow negative or zero tare.

CTARE

YES
NO

Allow CLEAR key to clear tare/accumulator.

PRTMOT

NO
YES

Allow print while in motion.

PRTPT

NO
YES

Add PT to keyed tare print.

OVRBAS

CALIB
SCALE

Zero base for overload calculation.

CALIB = Calibrate Zero
SCALE = Scale Zero

AGENCY

NTEP
CANADA
INDUST
NONE
OIML

Selects the agency having jurisdiction over the scale site.

OIML, NTEP, and CANADA modes allow a tare to be acquired at any weight greater than
zero. NONE allows tares to be acquired at any weight value. A tare can be cleared only if
the gross weight is at no load. NONE allows tares to be cleared at any weight value.

NTEP and OIML modes allow a new tare to be acquired even if a tare is already present.
In OIML mode, printing is not allowed if the scale is more than -20dd.

In CANADA mode, the previous tare must be cleared before a new tare can be acquired.

NONE, NTEP and CANADA modes allow the scale to be zeroed in either gross or net
mode as long as the current weight is within the specified ZRANGE. In OIML mode, the
scale must be in gross mode before it can be zeroed; pressing ZERO in net mode clears
the tare.

INDUST provides a set of subparameters to allow customization of tare, clear, and print
functions in non-legal-for-trade applications.

The value specified for this parameter affects the function of the front panel TARE and ZERO
keys. See Section 9.9 on page 97 for more information.
When in legal-for-trade mode, refer to Section 9.10 on page 98 for more information.