7 unpacking, Section 2. locating the appliance, 1 locating the appliance – LAARS MagnaTherm MGV - Installation, Operation and Maintenance Instructions User Manual

Page 11

Advertising
background image

MagnaTherm Boilers and Water Heaters

Page 7

Section 2
LOCATING THE APPLIANCE

2.1

Locating the Appliance

The MagnaTherm may be installed indoors or
outdoors. If installing outdoors in a location that
may experience freezing temperatures, precautions
must be taken to prevent water in the heat exchanger
and condensate inside and outside of the boiler from
freezing. Damage due to freezing water or condensate
is not covered by the warranty.

Choose a location for the unit which allows clearances
on all sides for maintenance and inspection. See Table 1.

Always install the unit on a firm, level surface.
The unit should not be located in an area where
leakage of any connections will result in damage to

the area adjacent to the appliance, or to lower floors
of the structure.

When this type of location is not available, install
a suitable drain pan, adequately drained, under the
appliance.
The appliance is design-certified by CSA-
International for installation on combustible

flooring; in basements; in utility rooms or alcoves.
MagnaTherm boilers must never be installed on
carpeting.
The location for the appliance should
be chosen with regard to the vent pipe lengths and
external plumbing.

The unit shall be installed such that the gas ignition
system components are protected from water (dripping,
spraying, rain, etc.) during operation and service
(circulator replacement, control replacement, etc.).

When vented vertically, the MagnaTherm must be
located as close as practical to the vertical section
of the vent. If the vent terminal and/or combustion
air terminal terminate through a wall, and there is
potential for snow accumulation in the local area, both
terminals should be installed at an appropriate level
above grade or the maximum expected snow line.

The dimensions and requirements that are shown in
Table 1 should be met when choosing the locations
for the appliance.

2.2

Correct Vent Distance from
Outside Wall or Roof Termination

The forced draft combustion air blower in the

appliance has sufficient power to vent properly when
the guidelines in Table 2

are followed.

1.7 Unpacking

The MagnaTherm is shipped in a single crate.

Remove all packing and tie-down materials.

Note -

When located on the same wall, the

MagnaTherm combustion air intake terminal must be

installed a minimum of 12” (

30cm)

below the exhaust

terminal. There must also be a minimum horizontal

distance from intake to the exhaust terminal

of 84” (

213cm)

See

Figure 4

APPLIANCE

SUGGESTED SERVICE ACCESS CLEARANCE

SURFACE INCHES

CM

Front

24

61

Left Side

8

20

Right Side

8

20

Back

24

61

Top, 2000

12

30

Top, 2500 & 3000

15

38

Top, 4000

24

61

APPLIANCE

REQUIRED CLEARANCE TO COMBUSTIBLES

SURFACE INCHES

CM

Front

18

45

Left Side

4

15

Right Side

4

15

Back

11

15

Top

1

2.5

Vent

1 2.5

Table 1.

Clearances

INTAKE / EXHAUST

MAX EQUIVALENT

SIZE DIAMETER FT.

M

2000 & 2500 8”

100

30

3000 & 3500 10”

100 30

4000 12”

100 30

Installations in the U.S. require exhaust vent pipe that is CPVC
complying with ANSI/ASTM D1785 F441, polypropylene
complying with ULC S636, or stainless steel complying with
UL1738. Installations in Canada require exhaust vent pipe that
is certified to ULC S636.
Intake (air) pipe must be PVC or CPVC that complies with
ANSI/ASTM D1785 F441, ABS that complies with ANSI/ASTM
D1527, stainless steel, or galvanized material.
To calculate max equivalent length, measure the linear feet of
the pipe, and add 5 feet (1.5 m) for each elbow used.

Table 2.

Vent / Air Pipe Sizes

Advertising
This manual is related to the following products: