Control settings for lead/lag system -part 1 – LAARS MagnaTherm MGV - Installation, Operation and Maintenance Instructions User Manual

Page 55

Advertising
background image

MagnaTherm Boilers and Water Heaters

Page 51

Figure 27. Lead / Lag Operation, 3 or more boilers

Low demand -

The first boiler in

sequence fires at

less than 65%

1

2

3

4

Demand increases -

Once the first boiler

reaches 50%,

the second boiler

switches on, and

both modulate

together between 29%

and 65%

Demand increases -

Once the first two

boilers reach 65%,

the third boiler

switches on, and all

boilers modulate together

between 29% and 65%. This continues as demand increases.

5

6

7

8

Nearing max. demand -

The last boiler becomes

active. Once all boilers

reach 65%, all are

allowed to go over

65%

The Lead/Lag controller will change the firing order of

the burners, based on the run time of each burner.

Number of boilers

installed

Base load value

1

NA

2

65%

3

50%

4

35%

5

35%

6

35%

7

35%

8

35%

Table 15. Base Load Settings

• When the Run sequence is initiated, the

boiler with the least amount of runtime

will fire.

• If the heating demand increases so that

the firing rate of that first boiler rises to

your boiler configurations Base Load
Value (see Table 15), the next boiler in

the sequence will start up and begin firing
at 20 to 35% fan speed (depending on

your configuration). After this, the entire

configuration of boilers will modulate
up or down together, in reaction to the
changes in demand.
See Figure 25 and Figure 27

Control Settings for Lead/Lag System -
Part 1

1. Power up all of the boilers in the system.

2. In an installation with several boilers, you

must give each boiler a different name,
sot that the controller of the Lead/Lag Master can
communicate with the other units. All of the units
come from the factory with a Modbus address of “1,”
so you will need to change some of these addresses.
On each unit, go to the screen for “System ID and
Access,” and enter a unique name.

3. The unit operating as the Lead/Lag Master must be

‘Master Enabled’ first and then set up address “1,” and
the other boilers should each be ‘Slave Enabled’ and
have unique Modbus address numbers typically 2 thru
X (total number of boilers)

On the boilers, touch the controller Icon on the Home

Screen.