Section 3. venting and combustion air, 1 combustion air, 1 combustion air from room – LAARS MagnaTherm MGV - Installation, Operation and Maintenance Instructions User Manual

Page 12: Laars heating systems

Advertising
background image

LAARS Heating Systems

Page 8

commencing within 12” (300 mm) of the top and
one commencing within 12” (300 mm) of the
bottom, of the enclosure shall be provided. The
openings shall communicate directly, or by ducts,
with the outdoors or spaces that freely communicate
with the outdoors. When directly communicating
with the outdoors, or when communicating to the
outdoors through vertical ducts, each opening shall
have a minimum free area of 1 square inch per
4000 Btu/hr (550 square mm/kW) of total input
rating of all equipment in the enclosure. When
communicating to the outdoors through horizontal
ducts, each opening shall have a minimum free
area of not less than 1 square inch per 2000 Btu/
hr (1100 square mm/kW) of total input rating of all
equipment in the enclosure.

Method 2: One permanent opening, commencing
within 12” (300 mm) of the top of the enclosure,
shall be permitted. The opening shall directly
communicate with the outdoors or shall
communicate through a vertical or horizontal duct
to the outdoors or spaces that directly communicate

Section 3
VENTING AND COMBUSTION AIR

3.1

Combustion Air

MagnaTherm boilers and water heaters must have
provisions for combustion and ventilation air in
accordance with the applicable requirements for
Combustion Air Supply and Ventilation in the

National Fuel Gas Code, ANSI Z223 1; or in Canada,
the Natural Gas and Propane Installation Code, CSA
B149.1. All applicable provisions of local building
codes must also be adhered to.

A MagnaTherms can take combustion air
from the space in which it is installed, or the
combustion air can be ducted directly to the unit.
Ventilation air must be provided in either case.

3.1.1

Combustion Air From Room

In the United States, the most common requirements
specify that the space shall communicate with the
outdoors in accordance with Method 1 or 2. (See the
following descriptions.) Where ducts are used, they
shall be of the same cross-sectional area as the free
area of the openings to which they connect.

Method 1: Two permanent openings, one

Table 3.

Ducted Air Accessories

(Place in section 3.1)

Model 2000

Model 2500

Model 3000

Model 3500

Model 4000

Screen for horizontal galvanized air pipe

D2012101

D2012101

D2012102

D2012103

D2012103

Screen for horizontal PVC air pipe

CA012001

CA012001

CA012002

CA012003

CA012003

Screen for horizontal polypropylene air pipe

CA012201

CA012201

CA012202

CA012203

CA012203

Screen for vertical galvanized air pipe

D2012201

D2012201

D2012202

D2012203

D2012203

Screen for vertical PVC air pipe

CA012401

CA012401

CA012402

CA012403

CA012403

Screen for vertical polypropylene air pipe

CA012601

CA012601

CA012602

CA012603

CA012603

Table 3a - Ducted Air Accessories

(Place in section 3.2)

Model 2000

Model 2500

Model 3000

Model 3500

Model 4000

Horizontal vent terminal for stainless steel

D2012001

D2012001

D2012002

D2012003

D2012003

Screen for horizontal CPVC vent

CA012101

CA012101

CA012102

CA012103

CA012103

Screen for vertical stainless steel vent

D2012301

D2012301

D2012302

D2012303

D2012303

Screen for vertical CPVC vent

CA012501

CA012501

CA012502

CA012503

CA012503

Table 3* - Vent Accessories

(Place in section 3.5)

Model 2000

Model 2500

Model 3000

Model 3500

Model 4000

Air intake screen for unit placed outdoors

CA011901

CA011901

CA011902

CA0011903

CA0011903

Vent terminal for unit placed outdoors

CA011801

CA011801

CA011802

CA011803

CA011803

Table 3** - Air & Vent Accessories for Units Placed Outdoors

Table 4.

Required Combustion Air Pipe Material

Material

United States

Canada

ABS

ANSI/ASTM D1527

The air pipe material must be chosen based upon

the intended application of the boiler, and must

be installed according to the vent manufacturer’s

installation instructions.

PVC, sch. 40

ANSI/ASTM D1785 or D2665

CPVC, sch. 40

ANSI/ASTM F441

Single wall galv. steel

26 gauge

Polypropylene

ULC S636 Class 2C