Dhw piping - two heaters, two vertical tanks, 6 mgv water flow, 7 condensate drain trap – LAARS MagnaTherm MGV - Installation, Operation and Maintenance Instructions User Manual

Page 31: Magnatherm boilers and water heaters

Advertising
background image

MagnaTherm Boilers and Water Heaters

Page 27

Figure 13. DHW Piping - Two Heaters, Two Vertical Tanks

NOTE:

This drawing shows

suggested piping configuration and

valving. Check with local codes and

ordinances for additional requirements.

Building

return

Supply

TPRV

2

Ball valve

(typical)

1

3

Cold water

supply

Expansion

tank

Pump

Pump

Check valve

Check valve

TPRV

7.6 MGV Water Flow

See Section 5 for water flow and head requirements.
Note - The head loss for the piping, fittings, and
accessories must be calculated and added to the
heater head loss to get the total required pump head.

An undersized pump will result in insufficient flow.
This can result in scale buildup and failure of the
heat exchanger.

7.7 Condensate Drain Trap

A condensate drain trap is included with the
MagnaTherm and is designed to drain the boiler of
condensate. The vent condensate should be drained
through a drain tee located in the vent line. This will
help prevent excessive condensate from entering the
boiler condensate trap.

Connect a 3/4” PVC pipe between the drain

connection and a floor drain (or condensate pump if a

floor drain is not accessible).

The condensate drain must be installed to
prevent the accumulation of condensate. When
a condensate pump is not used, the tubing must
continuously slope downward toward the drain with
no spiraling.

Consult local codes for the disposal method.

Caution

Condensate is mildly acidic (pH=5), and

may harm some floor drains and/or pipes,

particularly those that are metal. Ensure

that the drain, drainpipe, and anything that

will come in contact with the condensate

can withstand the acidity, or neutralize

the condensate before disposal. Damage
caused by failure to install a neutralizer
kit or to adequately treat condensate will
not be the manufacturer’s responsibility.

NOTES:

1. Locate the MGV DHW sensor

or remote aquastat well

in lower 1/3 of tank.

2. Back flow preventer may be

required - check local codes.

3. Thermal expansion tank may be

required - check local codes.

4.

Caution:

Pump sizing must

be based upon water

hardness at job site.

5. If the tank does not have a tapping for

the cold water supply, the supply may

be run to the pipe between the tank

and boiler inlet.

6. Common piping must be sized for

the combined water flow of all the

heaters.

Advertising
This manual is related to the following products: