4 vertical combustion air terminal, 4 common vent test – LAARS MagnaTherm MGV - Installation, Operation and Maintenance Instructions User Manual

Page 18

Advertising
background image

LAARS Heating Systems

Page 14

3.3.4

Vertical Combustion Air Terminal

When combustion air is taken from the roof, a field-
supplied rain cap or an elbow arrangement must be
used to prevent entry of rain water. The opening on
the end of the terminal must be at least 12” (30 cm)
above the point at which it penetrates the roof, and
high enough above the roof line to prevent blockage
from snow. When the vent terminates on the roof, the
combustion air must terminate at least 12” (30 cm)
below the vent terminal.

3.3.5

Installations in the Commonwealth
of Massachusetts

In Massachusetts the following items are required
if the side-wall exhaust vent termination is less than

seven (7) feet above finished grade in the area of
the venting, including but not limited to decks and
porches. (From Massachusetts Rules and regulations
248 CMR 5.08.)

1. Installation of Carbon Monoxide Detectors

At the time of installation of the side wall vented
gas fueled appliance, the installing plumber or

gas-fitter shall observe that a hard-wired carbon
monoxide detector with an alarm battery back-

up is installed on the floor level where the gas
appliance is to be installed. In addition, the

installing plumber or gasfitter shall observe
that a battery operated or hard-wired carbon
monoxide detector with an alarm is installed on
each additional level of the dwelling, building
or structure served by the side-wall horizontally
vented gas fueled equipment. It shall be the
responsibility of the property owner to secure

the services of qualified licensed professionals
for installation of hard-wired carbon monoxide
detectors.

a. In the event that the side-wall horizontally
vented gas fueled equipment is installed in a
crawl space or an attic, the hard-wired carbon
monoxide with alarm and battery back-up may

be installed on the next adjacent floor level.

b. In the event that the requirements of the
subdivision cannot be met at the time of
completion of installation, the owner shall have
a period of thirty (30) days to comply with the
above requirements, provided, however, that
during said thirty (30) day period, a battery
operated carbon monoxide detector with an
alarm be installed.

2. Approved Carbon Monoxide Detectors

Each carbon monoxide detector shall comply
with NFPA 720 and be ANSI/UL 2034 listed and

IAS certified.

3. Signage

A metal or plastic identification plate shall be
permanently mounted to the exterior of the
building at a minimum height of eight (8) feet
above grade directly in line with the exhaust
vent terminal for horizontally vented gas fueled
heating appliance or equipment. The sign shall
read, in print no less than one-half (1/2) inch in
size: “GAS VENT DIRECTLY BELOW, KEEP
CLEAR OF ALL OBSTRUCTIONS.”

4. Inspection

The state or local gas inspector of the side-
wall horizontally vented gas fueled appliance
shall not approve the installation unless, upon
inspection, the inspector observes carbon
monoxide detectors and signage installed in
accordance with the provisions of 248 CMR
5.08(2)(a) 1-4.

3.4

Common Vent Test

Note -

This section does not describe a method

for common venting MagnaTherm’s. It describes

what must be done when a unit is removed from

a common vent system. MagnaTherm’s require

special vent systems and fans for common vent.

Contact the factory if you have questions about

common venting MagnaTherm’s.

Figure 6. Combustion Air and Vent Through Roof

*

*

*

*

*

*

*

In Canada, refer to CAN/CSA

B199.1

Advertising
This manual is related to the following products: