Menu 4. Login Required


The screen used to Login is similar to the Keyboard
screen.
It may be difficult for some operators to press the
keys on this screen. In this case, use the back of a
plastic pen, or a stylus, or a pencil eraser. (Do not
use sharp metal tools – these may damage the plastic
surface of the screen.)

Each time you press a key, the system will respond
with a beep. If you are entering a password, an
asterisk (*) will appear for each character you enter.
The beeps and asterisks will help you enter the
correct number of characters for your password.

When changing a numerical value, the system
presents a numerical entry screen, as shown below.

Menu 5. Numeric Entry Screen

9.3

Verification Process for Safety-
Related Parameters

The verification process allows the user to

confirm that all the changes made are correct
and that there have not been any inadvertent
changes made.

1.

When you start to change a parameter that
is related to safety, the system will present a
warning which looks like this:

Menu 6. Parameter Safety Warning

WARNING

Changing safety parameters should only be

conducted by experienced, licensed boiler operators

and mechanics. Hazardous burner conditions can

happen with improper operations that may result in

PROPERTY LOSS, PHYSICAL INJURY, or DEATH.

Press OK to continue. The system will ask
you to login before you make a change. (For
more information on logging in, see Section
8.2.)

2.

If you make a change in any group that could
affect the safe operation of the unit, the control
system will ask you to “verify” the change
before it is accepted.

3.

Once all parameters have been changed, return

to the configure menu. In the lower right hand
corner of the screen you will see ‘VERIFY’
Press VERIFY, then press BEGIN to start

verification.

Notes –

• Once you change one of these safety-related

parameters, you must finish the verification

process for the group that includes the parameter,
or the control system will not let the boiler
operate

. You can wait to do the verification until

you have changed parameters in other groups, but

before you return the boiler to service, you must

complete the verification process for all groups

that have been changed.

• At the end of the verification process, you

must press the Reset button on the front of the

controller. See Figure 24. You have to do this

within 30 seconds, or the verification will be

cancelled. To make it easy to reach the Reset

button, open the door on the front of the boiler and

slide out the control panel before beginning the

verification.