MagnaTherm Boilers and Water Heaters

Page 71

Code

Description

Lockout

or Hold

Procedure

26

Internal fault:
Static flame ripple

H

Internal fault

1. Reset module

2. If fault repeats, replace module.

27

Internal fault:

Flame rod shorted to ground detected

H

Internal fault

1. Reset module

2. If fault repeats, replace module.

28

Internal fault:

A/D linearity test fails

H

Internal fault

1. Reset module

2. If fault repeats, replace module.

29

Internal fault:

Flame bias cannot be set in range

H

Internal fault

1. Reset module

2. If fault repeats, replace module.

30

Internal fault:

Flame bias shorted to adjacent pin

H

Internal fault

1. Reset module

2. If fault repeats, replace module.

31

Internal fault:

SLO electronics unknown error

H

Internal fault

1. Reset module

2. If fault repeats, replace module.

32-46 Internal fault:

Safety Key 0 through 14

L

Internal fault

1. Reset module

2. If fault repeats, replace module.

47

Flame Rod to ground leakage

H

Internal fault

1. Reset module

2. If fault repeats, replace module.

48

Static flame (not flickering)

H

Internal fault

1. Reset module

2. If fault repeats, replace module.

49

24 VAC voltage low/high

H

1. Check the module and display connections.

2. Check the module power supply and make
sure that frequency, voltage and VA meet the

specifications.

50

Modulation fault

H

Internal sub-system fault.

1. Review alert messages for possible trends.

2. Correct possible problems.

51

Pump fault

H

Internal sub-system fault.

1. Review alert messages for possible trends.

2. Correct possible problems.

52

Motor tachometer fault

H

Internal sub-system fault.

1. Review alert messages for possible trends.

2. Correct possible problems.