MagnaTherm Boilers and Water Heaters

Page 81

Code

Description

Lockout

or Hold

Procedure

214

Invalid Prepurge time setting

L

1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.

2. If fault repeats, verify electrical grounding.

3. If fault repeats, replace module.

215

Invalid Purge rate proving setting

L

1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.

2. If fault repeats, verify electrical grounding.

3. If fault repeats, replace module.

216

Invalid Run flame failure response
setting

L

1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.

2. If fault repeats, verify electrical grounding.

3. If fault repeats, replace module.

217

Invalid Run stabilization time setting

L

1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.

2. If fault repeats, verify electrical grounding.

3. If fault repeats, replace module.

218

Invalid Stack limit enable setting

L

1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.

2. If fault repeats, verify electrical grounding.

3. If fault repeats, replace module.

219

Invalid Stack limit response setting

L

1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.

2. If fault repeats, verify electrical grounding.

3. If fault repeats, replace module.

220

Unconfigured Delta T limit setpoint
setting

L

1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.

2. If fault repeats, verify electrical grounding.

3. If fault repeats, replace module.

221

Unconfigured DHW (Domestic Hot
Water) high limit setpoint setting

L

1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.

2. If fault repeats, verify electrical grounding.

3. If fault repeats, replace module.

222

Unconfigured Outlet high limit setpoint
setting

L

1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.

2. If fault repeats, verify electrical grounding.

3. If fault repeats, replace module.

223

Unconfigured Stack limit setpoint
setting

L

1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.

2. If fault repeats, verify electrical grounding.

3. If fault repeats, replace module.

224

Invalid DHW (Domestic Hot Water)
demand source setting

L

1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.

2. If fault repeats, verify electrical grounding.

3. If fault repeats, replace module.