MagnaTherm Boilers and Water Heaters

Page 83

Code

Description

Lockout

or Hold

Procedure

237

Invalid DHW (Domestic Hot Water)
connector type setting

L

1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.

2. If fault repeats, verify electrical grounding.

3. If fault repeats, replace module.

238

Invalid Stack connector type setting

L

1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.

2. If fault repeats, verify electrical grounding.

3. If fault repeats, replace module.

239

Invalid Header connector type setting

L

1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.

2. If fault repeats, verify electrical grounding.

3. If fault repeats, replace module.

240

Invalid Outdoor connector type setting

L

1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.

2. If fault repeats, verify electrical grounding.

3. If fault repeats, replace module.

12.3

Diagnostic Tests and Input/
Output Indicators

Two kinds of screens are grouped together in this
section:

• Detailed indications of the input and output

signals

• Diagnostic tests of the pumps and burner

modulation

Note that these functions apply to just one selected
controller.

To access the diagnostic functions, from the home
screen, touch the control icon, then touch the
‘Diagnostics’ button.

1.

The buttons at the bottom of the screen select
the types of inputs and outputs displayed. The
Burner Control I/O button leads to Menu 36

Menu 36. Burner Control I/O Screen

A green dot indicates a function that is “on.”

2.

Press the Digital I/O button to see parameters
with the functions that are either “on” or “off.”
See Menu 37.

Menu 37. Digital I/O Screen

3.

The button for Analog I/O displays items that
change continuously between two limits. See
Menu 38

Advertising