LAARS Heating Systems

Page 60

8.

MagnaTherm is equipped with a zero
governing, negative regulator valve. The valve

throttle should be adjusted only at high fire,
and the offset adjustment is only to be done at

low fire. From the “Home” screen touch the
control icon, then touch, Diagnostics. On the
I/O status screen press “Diagnostic Tests” and
enter the installer password by pressing the
padlock in the upper right corner.

Menu 26. Burner Status

Menu 27. I/0 Status

9.

From here you can manually adjust the fan
speed by pressing either the “Maximum
Modulation” or “Minimum Modulation”
buttons, then the “Start Test” button. In this

mode the boiler will run at the selected firing

rate for a period of five minutes or until the
“Stop Test” button is pressed. The fan speed
control feature is only active when the boiler

is in “Run” mode. To setup high fire select
“maximum modulation”, then “Start Test”
buttons. Wait for the boiler to enter run and
the fan speed to reach the maximum RPM.
Using a combustion analyzer, dial in the high

fire throttle to obtain the correct CO2 and CO
measurements. (refer to table 16 for correct
CO2 ranges).

Menu 28. Modulation Test

10. Once high fire is setup correctly select

“Minimum Modulation” and wait for the
fan speed to reach minimum RPM. When

at low fire adjust the offset screw to adjust

the low fire CO2 to the correct values.
(refer to table 16 for correct CO2 ranges)

11. After the setup for High and Low fire have

been completed, head back to the “Firing
Rate” menu, and select “Automatic”. This
MUST be done to ensure proper boiler
operation.