4 mgh suggested piping schematics, 5 condensate drain trap – LAARS MagnaTherm MGV - Installation, Operation and Maintenance Instructions User Manual

Page 24

Advertising
background image

LAARS Heating Systems

Page 20

Different glycol products may provide varying
degrees of protection. Glycol products must
be maintained properly in a heating system, or
they may become ineffective. Consult the glycol

specifications, or the glycol manufacturer, for

information about specific products, maintenance
of solutions, and set up according to your particular
conditions.

The following manufacturers offer glycols,
inhibitors, and anti foamants that are suitable
for use in the MagnaTherm. Please refer to the
manufacturers instructions for proper selection and
application.

Sentinel Performance Solutions Group

Hercules Chemical Company

Dow Chemical Company

The boiler control offers some assistance with freeze
protection, as long as the boiler is energized, and

able to fire.

1. If the outlet sensor detects less than 45

°F, the

control energizes the boiler pump.

2. If the outlet sensor detects less than 35

°F, the

control will fire at low rate.

3. Once in freeze protect mode, the boiler will

remain in that state until the outlet sensor detects
greater than 50

°F.

6.4 MGH Suggested Piping Schematics

Figure 7 through Figure 10 show suggested piping

configurations for MGH boilers. These diagrams
are only meant as guides. All components or piping
required by local code must be installed.

6.5

Condensate Drain Trap

A condensate drain trap is included with the
MagnaTherm and is designed to drain the boiler of
condensate. The vent condensate should be drained
through a drain tee located in the vent line. This will
help prevent excessive condensate from entering the
boiler condensate trap.

Connect a 3/4” PVC pipe between the drain

connection and a floor drain (or condensate pump if

a floor drain is not accessible).

The condensate drain must be installed to prevent
the accumulation of condensate. When a condensate
pump is not used, the tubing must continuously
slope downward toward the drain with no spiraling.

Consult local codes for the disposal method.

Caution

Condensate is mildly acidic (pH=5), and

may harm some floor drains and/or pipes,

particularly those that are metal. Ensure

that the drain, drainpipe, and anything that

will come in contact with the condensate

can withstand the acidity, or neutralize

the condensate before disposal. Damage
caused by failure to install a neutralizer
kit or to adequately treat condensate will
not be the manufacturer’s responsibility.

Advertising
This manual is related to the following products: