LAARS MagnaTherm MGV - Installation, Operation and Maintenance Instructions User Manual

Page 74

Advertising
background image

LAARS Heating Systems

Page 70

Code

Description

Lockout

or Hold

Procedure

11

Internal fault:
Invalid burner control state flag

L

Internal fault

1. Reset module

2. If fault repeats, replace module.

12

Internal fault:

Safety relay drive cap short

H

Internal fault

1. Reset module

2. If fault repeats, replace module.

13

Internal fault:

PII (Pre-Ignition Interlock) shorted to
ILK (Interlock)

H or L

Internal fault

1. Reset module

2. If fault repeats, replace module.

15

Internal fault:

Safety relay test failed due to feedback
ON

L

Internal fault

1. Reset module

2. If fault repeats, replace module.

16

Internal fault:

Safety relay test failed due to safety
relay OFF

L

Internal fault

1. Reset module

2. If fault repeats, replace module.

17

Internal fault:

Safety relay test failed due to safety
relay not OFF

L

Internal fault

1. Reset module

2. If fault repeats, replace module.

18

Internal fault:

Safety relay test failed due to feedback
not ON

L

Internal fault

1. Reset module

2. If fault repeats, replace module.

19

Internal fault:

Safety RAM write

L

Internal fault

1. Reset module

2. If fault repeats, replace module.

20

Internal fault:
Internal fault: Flame ripple and overflow

H

Internal fault

1. Reset module

2. If fault repeats, replace module.

21

Internal fault:

Flame number of sample mismatch

H

Internal fault

1. Reset module

2. If fault repeats, replace module.

22

Internal fault:

Flame bias out of range

H

Internal fault

1. Reset module

2. If fault repeats, replace module.

23

Internal fault:

Bias changed since heating cycle starts

H

Internal fault

1. Reset module

2. If fault repeats, replace module.

24

Internal fault:

Spark voltage stuck low or high

H

Internal fault

1. Reset module

2. If fault repeats, replace module.

25

Internal fault:

Spark voltage changed too much during

flame sensing time

H

Internal fault

1. Reset module

2. If fault repeats, replace module.

Advertising
This manual is related to the following products: