Section 8. electrical connections, 1 installation warnings, 2 main power connections – LAARS MagnaTherm MGV - Installation, Operation and Maintenance Instructions User Manual

Page 32

Advertising
background image

LAARS Heating Systems

Page 28

Section 8
ELECTRICAL CONNECTIONS

8.1 Installation Warnings

CAUTION

The supply voltage to the MagnaTherm unit

must not be disconnected, except for service

or isolation, or unless otherwise instructed by

procedures outlined in this manual. To signal

a call for heat, use the 24V field interlock, as

shown in the wiring diagram.

DO NOT MAKE AND BREAK THE LINE

VOLTAGE TO THE MagnaTherm UNIT TO

SIGNAL A CALL FOR HEAT. A call for heat/

end call for heat MUST be connected to the

field interlock terminals. Some MagnaTherm

components are designed to have constant

voltage during normal operation. If the

MagnaTherm’s supply voltage is toggled as a

call for heat signal, premature failure of these

components may result.

The MagnaTherm unit does not recognize 4mA

as a signal to shut off. If the call for heat is not

connected between the field interlock terminals,

the MagnaTherm will remain in low fire when it

sees 4mA as a modulating signal.

8.2 Main Power Connections

Magnatherm is provided with an electrical junction
box in the rear panel for easy connections and all
wires are factory installed between this junction box
and the Main High Voltage Box. The Magnatherm
line is equipped with multiple voltage packages to
adapt to customer needs ranging from 120-600 volts
with single or 3 phase versions. Refer to the rating
plate for appropriate voltage and current ratings.
As a common industry practice, LAARS has color
coded the single and three phase wires.

WARNING

The appliance must be electrically grounded in

accordance with the requirements of the authority

having jurisdiction or, in the absence of such

requirements, with the latest edition of the National

Electrical Code, ANSI/NFPA 70, in the U.S. and

with the latest edition of CSA C22.1 Canadian

Electrical Code, Part 1, in Canada. Do not rely

on the gas or water piping to ground the metal

parts of the boiler. Plastic pipe or dielectric unions

may isolate the boiler electrically. Service and

maintenance personnel, who work on or around

the boiler, may be standing on wet floors and

could be electrocuted by an ungrounded boiler.

Electrocution can result in severe injury or death.

Single pole switches, including those of safety

controls and protective devices, must not be wired

in a grounded line.

All electrical connections are made on the terminal

blocks that are located inside the control panel.

Wiring connections are shown in Figure 34.

All internal electrical components have been

prewired. No attempt should be made to connect

electrical wires to any other location except the

terminal blocks.