*When vent terminal is less than 10 feet (3 m) horizontally

from a forced air inlet, the terminal must be at least 3 feet

(0.9 m) above the air inlet. (US only)

Figure 3. Combustion Air and Vent Through Side Wall

U.S. Installations (see note 1)

Canadian Installations (see note 2)

A=

Clearance above grade, veranda, porch,

12 inches (30 cm)

12 inches (30 cm)

deck, or balcony

See note 6

See note 6

B=

Clearance to window or door that may be Direct vent only: 12 inches (30 cm);

36 inches (91 cm)

opened

Other than Direct vent: 4 ft (1.2m) below or to

side of opening; 1 ft (30 cm) above opening

C=

Clearance to permanently closed window

See note 4

See note 5

D=

Vertical clearance to ventilated soffit located

above the terminal within a horizontal

See note 4

See note 5

distance of 2 feet (61 cm) from the center

line of the terminal

E=

Clearance to unventilated soffit

See note 4

See note 5

F=

Clearance to outside corner

See note 4

See note 5

G=

Clearance to inside corner

See note 4

See note 5

H=

Clearance to each side of center line

3 feet (91 cm) within a height 15 feet

extended above meter/regulator assembly See note 4

above the meter/regulator assembly

I=

Clearance to service regulator vent outlet

See note 4

3 feet (91 cm)

J=

Clearance to nonmechanical air supply

Direct vent only: 36” (91cm)

inlet to building or the combustion air inlet Other than Direct vent: 4 ft (1.2m) below

36 inches (91 cm)

to any other appliance

or to side of opening; 1 ft (30 cm) above opening

K=

Clearance to a mechanical air supply inlet 3 feet (91 cm) above if within 10 feet (3 m)

6 feet (1.83 m)

horizontally

L=

Clearance above paved sidewalk or paved Vent termination not allowed in this location

7 ft (2.1 m)

driveway located on public property

for category IV appliances.

See note 5

M=

Clearance under veranda, porch, deck,

See note 4

12 inches (30 cm)

or balcony

See note 5

Notes:
1. In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code.
2. In accordance with the current CAN/CSA-B149 Installation Codes.
3. Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
4. For clearances not specified in ANSI Z223.1 / NFPA 54, clearance is in accordance with local installation codes and the
requirements of the gas supplier.
5. For clearances not specified in CAN/CSA-B149, clearance is in accordance with local installation codes and the requirements of the

gas supplier.
6. IMPORTANT: All terminals must be placed so that they remain a minimum 12” above expected snow line. Local codes may have

more specific requirements, and must be consulted.