5 outdoor installation, Section 4. gas supply and piping, 0 gas supply and piping – LAARS MagnaTherm MGV - Installation, Operation and Maintenance Instructions User Manual

Page 20

Advertising
background image

LAARS Heating Systems

Page 16

WARNING

Do not use open flame to check for leaks. An

open flame could lead to explosion, which

could result in property damage, serious injury

or death.

Note -

The MagnaTherm appliance and all

other gas appliances sharing the gas supply line

must be firing at maximum capacity to properly

measure the inlet supply pressure. The pressure

can be measured at the supply pressure port

on the gas valve. Low gas pressure could be an

indication of an undersized gas meter, undersized

gas supply lines and/or an obstructed gas supply

line. MagnaTherm units may be equipped with

low and high gas pressure switches that are

integrally vent limited. These types of devices do

not require venting to atmosphere.

Section 4
GAS SUPPLY AND PIPING

4.0

Gas Supply and Piping

Gas piping should be supported by suitable hangers

or floor stands, not the appliance. Installers should
refer to local building and safety codes or, in the
absence of such requirements, follow the National
Fuel Gas Code, ANSI Z223.1 NFPA and/or CSA
B149.1 installation codes.

Review the following instructions before proceeding

with the installation.

1. Verify that the appliance is fitted for the

proper type of gas by checking the rating
plate. MagnaTherm appliances are normally
equipped to operate at elevations up to 2000
feet (610m).
However, the appliance will function properly

without the use of high altitude modification at
elevations up to 10,000 feet (3050 m).

2.

The maximum inlet gas pressure must not
exceed 13” W.C. (3.2kPa). The minimum inlet
gas pressure is 4” W.C. (1.0kPa).

3.

Table 8 and Table 9 offer some gas pipe sizing
information. Refer to the applicable gas code
for more detailed sizing information.

4.

Run gas supply line in accordance with all
applicable codes.

5.

Locate and install manual shutoff valves in
accordance with state and local requirements.

6.

A sediment trap must be provided upstream of
the gas controls.

7.

All threaded joints should be coated with
piping compound resistant to action of

liquefied petroleum gas.

8.

The appliance and its individual shutoff valve
must be disconnected from the gas supply
piping during any pressure testing of that
system at test pressures in excess of 1/2 PSIG
(3.45kpa).

9.

The unit must be isolated from the gas supply
system by closing its individual manual shutoff
valve during any pressure testing of the gas
supply piping system at test pressures equal to
or less than 1/2 PSIG (3.45kpa).

10. The appliance and its gas connection must be

leak tested before placing it in operation.

11. Purge all air from gas lines

3.5

Outdoor Installation

If installing outdoors in a location that may experience
freezing temperatures, precautions must be taken to
prevent water in the heat exchanger and condensate
inside and outside of the boiler from freezing. Damage
due to freezing water or condensate is not covered by the
warranty.

For proper operation in outdoor installations,
the boiler must be equipped with the inlet air and
exhaust terminal kits listed in Table 7. Additional
instructions are supplied with the terminal kits.

Table 7.

Air & Vent accessories for Units Placed Outdoors

(Place in section 3.1)

Model 2000

Model 2500

Model 3000

Model 3500

Model 4000

Screen for horizontal galvanized air pipe

D2012101

D2012101

D2012102

D2012103

D2012103

Screen for horizontal PVC air pipe

CA012001

CA012001

CA012002

CA012003

CA012003

Screen for horizontal polypropylene air pipe

CA012201

CA012201

CA012202

CA012203

CA012203

Screen for vertical galvanized air pipe

D2012201

D2012201

D2012202

D2012203

D2012203

Screen for vertical PVC air pipe

CA012401

CA012401

CA012402

CA012403

CA012403

Screen for vertical polypropylene air pipe

CA012601

CA012601

CA012602

CA012603

CA012603

Table 3a - Ducted Air Accessories

(Place in section 3.2)

Model 2000

Model 2500

Model 3000

Model 3500

Model 4000

Horizontal vent terminal for stainless steel

D2012001

D2012001

D2012002

D2012003

D2012003

Screen for horizontal CPVC vent

CA012101

CA012101

CA012102

CA012103

CA012103

Screen for vertical stainless steel vent

D2012301

D2012301

D2012302

D2012303

D2012303

Screen for vertical CPVC vent

CA012501

CA012501

CA012502

CA012503

CA012503

Table 3* - Vent Accessories

(Place in section 3.5)

Model 2000

Model 2500

Model 3000

Model 3500

Model 4000

Air intake screen for unit placed outdoors

CA011901

CA011901

CA011902

CA0011903

CA0011903

Vent terminal for unit placed outdoors

CA011801

CA011801

CA011802

CA011803

CA011803

Table 3** - Air & Vent Accessories for Units Placed Outdoors

Advertising