MagnaTherm Boilers and Water Heaters

Page 29

Three Phase

Single Phase

600

480

208

120

240

L1

P

BR

Blk

L1

Blk

Blk

L2

V

O

R

L2

Wht

R

L3

T

Y

BL

Table 12.

Phase Voltage Color Identification

On three phase models a step down transformer
(which is protected using an appropriate din rail
mounted circuit breaker) generates 120 volt single
phase to power the 24 Volt Transformer. The 120
volt and 24 volt outputs of either transformer are
protected with resettable fuses mounted in the top
of the high voltage box. The 24 volt transformer is
also redundantly protected by its integrated 4 amp
resettable fuse.

On single phase models, the incoming voltage will
be protected by the appropriate circuit breaker sized

and installed, by a qualified Electrician/authorized
personnel. The 120 volt and 24 volt systems will be
protected with resettable fuses mounted in the top
of the high voltage box. The 24 volt transformer is
also redundantly protected by its integrated 4 amp
resettable fuse.

8.3 Pump Connections and Operation

The controller in the Magnatherm energizes the
appropriate pump contacts when it receives a call for

heat. Once the call for heat is satisfied, the pumps

will remain on for the defined pump overrun time.
The Boiler, System, and DHW pump terminals
are found on the Main control board TB1-15A
through 20A. They are fed 120 Volts internally
from the main power feed. The current rating
of the contacts is 7.4 amps, and an appropriately
sized contactor must be supplied and installed

by a qualified technician to ensure proper pump
operation. Once the system has been installed, the

“Pump Configuration” menu will allow the installer
to adjust Pump control, Overrun time and Demand
control for the various pumps in the system.

Caution

The supply voltage to the MagnaTherm must

not be disengaged, except for service or

isolation, or unless otherwise instructed by

procedures outlined in this manual. To signal

a call for heat, use the correct terminals as

instructed in Section 8.

Table 13. Electrical Data

Model

2000

2500 / 3000

3500 / 4000

Voltage

120

220

208 3

ш

480 3

ш

600 3

ш

120

220

208 3

ш

480 3

ш

600 3ш 120

220

208 3

ш

480 3

ш

600 3

ш

Nominal
Current

15.1 8.8

7.0

3.2

2.8

N/A N/A

12.5

5.0

4.0

N/A N/A

113

4.8

4.4

FLA

22.6 11.3

12.7

6.2

4.5

N/A N/A

19.4

8.7

5.9

N/A N/A

19.4

8.7

5.9

Caution

Label all wires prior to disconnection when

servicing controls. Wiring errors can cause

improper and dangerous operation. Verify

proper operation after operation servicing.

Attention

Au moment de l’entretien des commandes,

étiquetez tous les fils avant de les

débrancher. Les erreurs de câblage

peuvent nuire au bon fonctionnement et

être dangereuses. S’assurer que l’appareil

fonctionne adéquatement une fois l’entretien

terminé.