3 model identification, 4 warranty, Model nomenclature – LAARS MagnaTherm MGV - Installation, Operation and Maintenance Instructions User Manual

Page 6: Laars heating systems

Advertising
background image

LAARS Heating Systems

Page 2

Model Nomenclature

1 2

3

4 5 6 7 8

9

10

11

12

13

M G

1

SERIES

M G

USAGE

H -

HYDRONIC

V -

VOLUME

WATER

SIZE

MBTU/h

2 0 0 0
2 5 0 0
3 0 0 0
3 5 0 0
4 0 0 0

FUEL

N -

NATURAL

P -

PROPANE

COUNTRY

CODE

X -

USA/

CANADA

E -

EXPORT

*

OPTIONS CODE

X -

STANDARD

J

- CSD-1

ELEC SYSTEM

A - 110V, 1Ø

B - 220V, 1Ø

C - 208V, 3Ø

D - 480V, 3Ø

E - 600V, 3Ø

REVISION

1 -FIRST

ASME

X -

“H” STAMP (MGH)

W -

“HLW” STAMP (MGV)

1.4 Warranty

LAARS Heating Systems MagnaTherm boilers are
covered by a limited warranty. The owner should
complete the warranty registration at

http://www.LAARS.com

ALL WARRANTY CLAIMS must be made by an
authorized LAARS Heating Systems representative.
Claims must include the serial number and model
(this information can be found on the rating plate).
All claims must also include the installation date and
name of the installer. Shipping costs are not included
in the warranty coverage.

1.3

Model Identification

Consult the rating plate on the unit. The following
information describes the model number structure.

(1-2) Model Series Designation

M G = MagnaTherm

(3) Usage

H = Hydronic

V = Volume Water

(4-7) Size

2 0 0 0 = 1,999,000 BTU/hr input

2 5 0 0 = 2,499,000 BTU/hr input

3 0 0 0 = 3,000,000 BTU/hr input

3 5 0 0 = 3,500,000 BTU/hr input

4 0 0 0 = 4,000,000 BTU/hr input

(8) Fuel

N = Natural Gas

P = LP Gas

(9) Country Code

X = USA / CANADA

E - Export (CE - non CSA)

(10) Option Code

X = Standard Unit

J = CSD1 Version

(11) Electrical System

A - 110V, (Single Phase)

B - 220V, (Single Phase)

C - 208V, (Three Phase)

D - 480V, (Three Phase)

E - 600V, (Three Phase)

(12) Additional Options

X - “H” STAMP (MGH)

W - “HLW” STAMP (MGV)

(13) Revision

1 = First

*

Not CSA approved

Altitude:

Gas input rating of the MagnaTherm shall be used for
elevations up to 2000 ft (600 m). The input rating at
elevations above 2000 ft (600 m) shall be reduced at
a rate of 4 percent for each 1000 ft (300 m) above sea
level before selecting the equipment size.

WARNING

Electrical Shock Hazard

Electrical shock can cause severe injury, death or

property damage. Disconnect the power supply

before beginning installation or changing the

wiring to prevent electrical shock or damage to the

equipment. It may be necessary to turn off more than

one power supply disconnect.

All electrical wiring is to be done in accordance with

local codes, or in the absence of local codes, with:

1) The National Electrical Code ANSI/NFPA No.

70 - latest Edition, or 2) CSA STD. C22.1 “Canadian

Electrical Code - Part 1.” This appliance must be

electrically grounded in accordance with these codes.

WARNING

MagnaTherm units must be installed in

accordance with the procedures detailed in this

manual, or the LAARS Heating Systems warranty

will be voided. The installation must conform to

the requirements of the local jurisdiction having

authority, and, in the United States, to the latest

edition of the National Fuel Gas Code, ANSI

Z223.1/NFPA54. In Canada, the installation

must conform to the latest edition of CSA

B149.1 Natural Gas and Propane Gas Installation

Code, and/or local codes. Where required by the

authority having jurisdiction, the installation

of MagnaTherm boilers must conform to the

Standard for Controls and Safety Devices for

Automatically Fired Boilers, ANSI/ASME CSD-1.

Any modifications to the boiler, its gas controls, or

wiring may void the warranty. If field conditions

require modifications, consult the factory

representative before initiating such modifications.