11 – combustion setup procedure – LAARS MagnaTherm MGV - Installation, Operation and Maintenance Instructions User Manual

Page 63

Advertising
background image

MagnaTherm Boilers and Water Heaters

Page 59

9.11 – Combustion Setup Procedure

In this section, we will explain how to set up the gas

valve so the boiler will run efficiently at both the
High Fire and Low Fire conditions.

Required tools: Screwdrivers, Torx bits, Allen
Wrench Set, Combustion Analyzer

WARNING

Improper adjustment may lead to poor combustion

quality, increasing the amount of carbon monoxide

produced. Excess carbon monoxide levels may

lead to personal injury or death.

1.

On the Main Gas Valve, locate the adjustments

for high fire throttle, and low fire offset. See
Fig. 98 and 99.
Refer to Table 17 for appropriate CO2 ranges.

2.

Press the Control Icon at the center of the
Home Screen

.

Menu 22. ‘Home’ screen

3.

The system will present the Status Summary
screen.

Menu 23. Status Summary Screen

4. Press the ‘Configure’ button in the lower left

corner.

Menu 24.

Configuration Menu

5. From the “Configuration” menu, select the line

“Burner Control Ignition.”

Menu 25. Burner Control Ignition

Once there select “Pilot Test Hold” and turn
this feature “ON.” This feature will allow
the pilot to stay lit for setup and will NEVER

fire the main burner. Give the unit a call for
heat and the boiler will begin its sequence of
operation (Refer to Section 12.8 for sequence
of operation, and Table 14 for required pilot
valve pressures.)

6.

Once the pilot has lit, adjust pilot regulator
pressure to that described in Table 14. With

pilot still lit, view the flame through the sight
glass. An adjustment to the pilot regulator

may be needed if a yellow flame is visible.
Use the regulator adjustment to adjust pilot

flame to a nice blue hue while ensuring that
the pressure in the pilot valve (See Table 14).

7.

Once the desired pilot has been established,
turn the call for heat OFF and return to

“Burner Control Ignition” in the “Configure”
menu to turn “OFF” the pilot test hold.