1 common venting, 3 venting requirements unique tocanada, Laars heating systems – LAARS MagnaTherm MGV - Installation, Operation and Maintenance Instructions User Manual

Page 14

Advertising
background image

LAARS Heating Systems

Page 10

If the system temperatures are unknown at the
time of installation, class IIC or higher venting
material is recommended.

The MagnaTherm is a Category IV appliance and
may be installed with the standards listed on Table 6.
The unit’s vent can terminate through the roof, or
through an outside wall.

All installations must be done following the vent
supplier’s recommended installation techniques.
If these are not available, refer to the LAARS
recommendations for the material used.

For Category IV boilers, have horizontal runs
sloping upwards not less than 1/4 inch per foot

(21 mm/m) from the boiler to the vent terminal;
be installed so as to prevent accumulation of

condensate; and, where necessary, have means
provided for drainage of condensate.

Pour la catégorie IV, les chaudières ont horizontal
en pente vers le haut au moins 1/4 de pouce par pied
(21 mm/m) à partir de la chaudière pour l’évent

borne; être installé de façon à éviter l’accumulation

de condensats; et, le cas échéant, ont des moyens
prévus pour l’évacuation des condensats.

This will allow the condensate to run back to the
MagnaTherm to drain. Route the vent pipe to the
heater as directly as possible. Seal all joints. Provide
adequate hangers as required in the venting system
manufacturer’s Installation Instructions, or at least
every 4 feet.

The unit must not support the weight of the vent
pipe. The maximum equivalent pipe length allowed
is 100 feet (30m). Each elbow is considered to be 5
feet (1.5m). LAARS offers accessories to use with
horizontal and vertical exhaust vent systems, as
shown in Table 5

3.2.1

Common Venting

The MagnaTherm can be common vented, however,
the common venting must be a professionally
designed and approved system. MagnaTherm
units are never permitted to share a vent with any
Catagory 1 appliances.

3.2.3

Venting Requirements Unique to
Canada

MagnaTherm boilers and water heaters are Vent

Table 5.

Vent Accessories

(Place in section 3.1)

Model 2000

Model 2500

Model 3000

Model 3500

Model 4000

Screen for horizontal galvanized air pipe

D2012101

D2012101

D2012102

D2012103

D2012103

Screen for horizontal PVC air pipe

CA012001

CA012001

CA012002

CA012003

CA012003

Screen for horizontal polypropylene air pipe

CA012201

CA012201

CA012202

CA012203

CA012203

Screen for vertical galvanized air pipe

D2012201

D2012201

D2012202

D2012203

D2012203

Screen for vertical PVC air pipe

CA012401

CA012401

CA012402

CA012403

CA012403

Screen for vertical polypropylene air pipe

CA012601

CA012601

CA012602

CA012603

CA012603

Table 3a - Ducted Air Accessories

(Place in section 3.2)

Model 2000

Model 2500

Model 3000

Model 3500

Model 4000

Horizontal vent terminal for stainless steel

D2012001

D2012001

D2012002

D2012003

D2012003

Screen for horizontal CPVC vent

CA012101

CA012101

CA012102

CA012103

CA012103

Screen for vertical stainless steel vent

D2012301

D2012301

D2012302

D2012303

D2012303

Screen for vertical CPVC vent

CA012501

CA012501

CA012502

CA012503

CA012503

Table 3* - Vent Accessories

(Place in section 3.5)

Model 2000

Model 2500

Model 3000

Model 3500

Model 4000

Air intake screen for unit placed outdoors

CA011901

CA011901

CA011902

CA0011903

CA0011903

Vent terminal for unit placed outdoors

CA011801

CA011801

CA011802

CA011803

CA011803

Table 3** - Air & Vent Accessories for Units Placed Outdoors

Installation Standards

Material

United States

Canada

Stainless steel

UL 1738

Venting must be ULC S636 certified for use as
venting material. The venting material class must
be chosen based upon the intended application
of the boiler, and must be installed according to
the maximum flue gas temperature and the vent
manufacturer’s instructions.

CPVC, sch 40

ANSI/ASTM F441

Polypropylene

Pending APPROVAL

ULC S636 Class 2C

Table 6.

Required Exhaust Vent Material

Advertising