17 lead lag slave configuration, Laars heating systems – LAARS MagnaTherm MGV - Installation, Operation and Maintenance Instructions User Manual

Page 54

Advertising
background image

LAARS Heating Systems

Page 50

Figure 25. Lead / Lag Operation, 2 boilers.

Low demand -

The first boiler in

sequence fires at

less than 65%

First

boiler

Second

boiler

Demand increases -

Once the first boiler

reaches 65%,

the second boiler

switches on, and

both modulate

together between 20%

and 65%

Nearing max. demand -

Once both reach 65%,

then they are both

allowed to go over

65%

9.7.17 Lead Lag Slave Configuration

About Lead/Lag Operation -

If an installation includes two or more boilers, they
may be set up for “Lead/Lag” operation. One boiler
will be set up as the “Master”, and the others will
operate as “Slaves.” Figure 26 shows an installation
with eight boilers. (A Lead/Lag system can include up
to eight boilers.) The boiler controllers are connected
in a “daisy chain” using a Modbus connection.

A single System sensor is used to monitor the demand
for heat. The input from this sensor is used by the
Master controller to control the modulation rates of all
of the operating boilers.

Lead/Lag Modulation Cycle -

Note - We will explain the modulation cycle here, in
case you need to understand how the Lead/Lag system
actually operates. If you are installing the unit(s)
and want to skip this section, just remember that, as
the heating demand increases, the Lead/Lag system
puts more boilers on-line. As the heating demand is
reduced, the Lead/Lag system shuts off some of the
boilers.

The signal from the System sensor is sent to the unit
operating as the Lead/Lag Master. A Run sequence is
initiated when the system temperature falls to the Lead/
Lag Central Heat setpoint. (Actually this is the LL
CH setpoint less the On Hysteresis value. The default
setting for On Hysteresis is 5°F, but this is adjustable.)

Notice that, when a boiler is operating as part of a
Lead/Lag system, it does not use the normal CH
setpoint – it uses the special LL CH setpoint on the
Lead/Lag Master.

The unit acting as the Lead/Lag Master

decides which boiler is assigned to start first. This
assignment is rotated across all of the available
boilers so that any one boiler does not run

significantly longer than the others. The Lead/Lag
controller tracks the run times for all of the boilers,
and uses this to calculate the starting order for the
boilers. This means that each time the system starts

up, a different boiler may start first.

Figure 26. “ Lead/Lag” Operation in a System with Eight Boilers. Note: The Displays on Boilers 2 thru 8

will display information pertaining only to that specific boiler.

Touch

Screen

Lead Lag

Master

Addr

1

Addr

2

Addr

3

Boiler 4

Addr

4

Boiler 5

Addr

5

Boiler 6

Addr

6

Boiler 7

Addr

7

Boiler 8

Addr

8

Boiler 3

Boiler 2

Boiler 1

Caution

You should set the Modbus addresses before

you connect the Modbus wiring. If the wiring

is attached before the Modbus addresses on

the controls are changed, there will be multiple

controls with the same address, and the system

will not work.

WARNING

If the Modbus addresses are not assigned

properly, the system could fail to operate

correctly, or it might operate in an unsafe

manner. This could lead to property damage,

personal injury or death.

Advertising
This manual is related to the following products: