MagnaTherm Boilers and Water Heaters

Page 17

SCHED 40 METAL PIPE CAPACITY FOR 1.50 SPECIFIC GRAVITY

UNDILUTED PROPANE

NOMINAL PIPE SIZE @ 11” W.C. INLET AND 0.5” W.C. PRESSURE

DROP

SCH 40 METAL PIPE CAPACITY FOR 0.60 SPECIFIC GRAVITY

NATURAL GAS

NOMINAL PIPE SIZE @ 0.30” W.C. PRESSURE DROP

Nominal:

2

3

4

5

Nominal:

2

3

4

Actual ID:

2.067

2.469

3.068

4.026

5.047

Actual ID:

1.61

2.067

2.469

3.068

4.026

Length (ft)

Length (ft)

10

4,020

6,400

11,300

23,100

41,800

10

3,520

6,790

10,800

19,100

39,000

20

2,760

4,400

7,780

15,900

28,700

20

2,420

4,660

7,430

13,100

26,800

30

2,220

3,530

6,250

12,700

23,000

30

1,940

3,750

5,970

10,600

21,500

40

1,900

3,020

5,350

10,900

19,700

40

1,660

3,210

5,110

9,030

18,400

50

1,680

2,680

4,740

9,660

17,500

50

1,480

2,840

4,530

8,000

16,300

60

1,520

2,430

4,290

8,760

15,800

60

1,340

2,570

4,100

7,250

14,800

70

1,400

2,230

3,950

8,050

14,600

80

1,230

2,370

3,770

6,670

13,600

80

1,300

2,080

3,670

7,490

13,600

100

1,140

2,200

3,510

6,210

124,700

90

1,220

1,950

3,450

7,030

12,700

125

1,070

2,070

3,290

5,820

11,900

100

1,160

1,840

3,260

6,640

12,000

150

1,010

1,950

3,110

5,500

11,200

125

1,020

1,630

2,890

5,890

10,600

175

899

1,730

2,760

4,880

9,950

150

928

1,480

2,610

5,330

9,650

200

814

1,570

2,500

4,420

9,010

175

854

1,360

2,410

4,910

8,880

250

749

1,440

2,300

4,060

8,290

200

794

1,270

2,240

4,560

8,260

300

697

1,340

2,140

3,780

7,710

150

704

1,120

1,980

4,050

7,320

350

618

1,190

1,900

3,350

6,840

300

638

1,020

1,800

3,670

6,630

400

560

1,080

1,720

3,040

6,190

350

587

935

1,650

3,370

6,100

Notes:

400

546

870

1,540

3,140

5,680

1. Inlet pressure - 11.0 in w.c.

Notes:

2. Pressure drop - 0.5 in w.c.

1. Inlet pressure - Less than 2 psi

3. Specific gravity - 1.50

2. Pressure drop - 0.5 in w.c.

4. Schedule 40 metallic pipe

3. Specific gravity - 0.60

5. Intended use - Pipe sizing between single- or second-stage

4. Schedule 40 metallic pipe

(low pressure) regulator and appliance.

Capacity in Cubic Feet of Gas per Hour

Pipe Size (in.)

Natural Gas

Undiluted Propane

Pipe Size (in.)

Capacity in Cubic Feet of Gas per Hour

Nominal:

2

3

4

5

Nominal:

2

3

4

Actual ID:

2.067

2.469

3.068

4.026

5.047

Actual ID:

1.61

2.067

2.469

3.068

4.026

Length (ft)

Length (ft)

10

4,020

6,400

11,300

23,100

41,800

10

3,520

6,790

10,800

19,100

39,000

20

2,760

4,400

7,780

15,900

28,700

20

2,420

4,660

7,430

13,100

26,800

30

2,220

3,530

6,250

12,700

23,000

30

1,940

3,750

5,970

10,600

21,500

40

1,900

3,020

5,350

10,900

19,700

40

1,660

3,210

5,110

9,030

18,400

50

1,680

2,680

4,740

9,660

17,500

50

1,480

2,840

4,530

8,000

16,300

60

1,520

2,430

4,290

8,760

15,800

60

1,340

2,570

4,100

7,250

14,800

70

1,400

2,230

3,950

8,050

14,600

80

1,230

2,370

3,770

6,670

13,600

80

1,300

2,080

3,670

7,490

13,600

100

1,140

2,200

3,510

6,210

124,700

90

1,220

1,950

3,450

7,030

12,700

125

1,070

2,070

3,290

5,820

11,900

100

1,160

1,840

3,260

6,640

12,000

150

1,010

1,950

3,110

5,500

11,200

125

1,020

1,630

2,890

5,890

10,600

175

899

1,730

2,760

4,880

9,950

150

928

1,480

2,610

5,330

9,650

200

814

1,570

2,500

4,420

9,010

175

854

1,360

2,410

4,910

8,880

250

749

1,440

2,300

4,060

8,290

200

794

1,270

2,240

4,560

8,260

300

697

1,340

2,140

3,780

7,710

150

704

1,120

1,980

4,050

7,320

350

618

1,190

1,900

3,350

6,840

300

638

1,020

1,800

3,670

6,630

400

560

1,080

1,720

3,040

6,190

350

587

935

1,650

3,370

6,100

Notes:

400

546

870

1,540

3,140

5,680

1. Inlet pressure - 11.0 in w.c.

Notes:

2. Pressure drop - 0.5 in w.c.

1. Inlet pressure - Less than 2 psi

3. Specific gravity - 1.50

2. Pressure drop - 0.5 in w.c.

4. Schedule 40 metallic pipe

3. Specific gravity - 0.60

5. Intended use - Pipe sizing between single- or second-stage

4. Schedule 40 metallic pipe

(low pressure) regulator and appliance.

Capacity in Cubic Feet of Gas per Hour

Pipe Size (in.)

Natural Gas

Undiluted Propane

Pipe Size (in.)

Capacity in Cubic Feet of Gas per Hour

Table 8.

Pipe Capacity for Natural Gas

Table 9.

Pipe Capacity for Propane

Nominal:

2

3

4

5

Nominal:

2

3

4

Actual ID:

2.067

2.469

3.068

4.026

5.047

Actual ID:

1.61

2.067

2.469

3.068

4.026

Length (ft)

Length (ft)

10

4,020

6,400

11,300

23,100

41,800

10

3,520

6,790

10,800

19,100

39,000

20

2,760

4,400

7,780

15,900

28,700

20

2,420

4,660

7,430

13,100

26,800

30

2,220

3,530

6,250

12,700

23,000

30

1,940

3,750

5,970

10,600

21,500

40

1,900

3,020

5,350

10,900

19,700

40

1,660

3,210

5,110

9,030

18,400

50

1,680

2,680

4,740

9,660

17,500

50

1,480

2,840

4,530

8,000

16,300

60

1,520

2,430

4,290

8,760

15,800

60

1,340

2,570

4,100

7,250

14,800

70

1,400

2,230

3,950

8,050

14,600

80

1,230

2,370

3,770

6,670

13,600

80

1,300

2,080

3,670

7,490

13,600

100

1,140

2,200

3,510

6,210

124,700

90

1,220

1,950

3,450

7,030

12,700

125

1,070

2,070

3,290

5,820

11,900

100

1,160

1,840

3,260

6,640

12,000

150

1,010

1,950

3,110

5,500

11,200

125

1,020

1,630

2,890

5,890

10,600

175

899

1,730

2,760

4,880

9,950

150

928

1,480

2,610

5,330

9,650

200

814

1,570

2,500

4,420

9,010

175

854

1,360

2,410

4,910

8,880

250

749

1,440

2,300

4,060

8,290

200

794

1,270

2,240

4,560

8,260

300

697

1,340

2,140

3,780

7,710

150

704

1,120

1,980

4,050

7,320

350

618

1,190

1,900

3,350

6,840

300

638

1,020

1,800

3,670

6,630

400

560

1,080

1,720

3,040

6,190

350

587

935

1,650

3,370

6,100

Notes:

400

546

870

1,540

3,140

5,680

1. Inlet pressure - 11.0 in w.c.

Notes:

2. Pressure drop - 0.5 in w.c.

1. Inlet pressure - Less than 2 psi

3. Specific gravity - 1.50

2. Pressure drop - 0.5 in w.c.

4. Schedule 40 metallic pipe

3. Specific gravity - 0.60

5. Intended use - Pipe sizing between single- or second-stage

4. Schedule 40 metallic pipe

(low pressure) regulator and appliance.

Capacity in Cubic Feet of Gas per Hour

Pipe Size (in.)

Natural Gas

Undiluted Propane

Pipe Size (in.)

Capacity in Cubic Feet of Gas per Hour

Nominal:

2

3

4

5

Nominal:

2

3

4

Actual ID:

2.067

2.469

3.068

4.026

5.047

Actual ID:

1.61

2.067

2.469

3.068

4.026

Length (ft)

Length (ft)

10

4,020

6,400

11,300

23,100

41,800

10

3,520

6,790

10,800

19,100

39,000

20

2,760

4,400

7,780

15,900

28,700

20

2,420

4,660

7,430

13,100

26,800

30

2,220

3,530

6,250

12,700

23,000

30

1,940

3,750

5,970

10,600

21,500

40

1,900

3,020

5,350

10,900

19,700

40

1,660

3,210

5,110

9,030

18,400

50

1,680

2,680

4,740

9,660

17,500

50

1,480

2,840

4,530

8,000

16,300

60

1,520

2,430

4,290

8,760

15,800

60

1,340

2,570

4,100

7,250

14,800

70

1,400

2,230

3,950

8,050

14,600

80

1,230

2,370

3,770

6,670

13,600

80

1,300

2,080

3,670

7,490

13,600

100

1,140

2,200

3,510

6,210

124,700

90

1,220

1,950

3,450

7,030

12,700

125

1,070

2,070

3,290

5,820

11,900

100

1,160

1,840

3,260

6,640

12,000

150

1,010

1,950

3,110

5,500

11,200

125

1,020

1,630

2,890

5,890

10,600

175

899

1,730

2,760

4,880

9,950

150

928

1,480

2,610

5,330

9,650

200

814

1,570

2,500

4,420

9,010

175

854

1,360

2,410

4,910

8,880

250

749

1,440

2,300

4,060

8,290

200

794

1,270

2,240

4,560

8,260

300

697

1,340

2,140

3,780

7,710

150

704

1,120

1,980

4,050

7,320

350

618

1,190

1,900

3,350

6,840

300

638

1,020

1,800

3,670

6,630

400

560

1,080

1,720

3,040

6,190

350

587

935

1,650

3,370

6,100

Notes:

400

546

870

1,540

3,140

5,680

1. Inlet pressure - 11.0 in w.c.

Notes:

2. Pressure drop - 0.5 in w.c.

1. Inlet pressure - Less than 2 psi

3. Specific gravity - 1.50

2. Pressure drop - 0.5 in w.c.

4. Schedule 40 metallic pipe

3. Specific gravity - 0.60

5. Intended use - Pipe sizing between single- or second-stage

4. Schedule 40 metallic pipe

(low pressure) regulator and appliance.

Capacity in Cubic Feet of Gas per Hour

Pipe Size (in.)

Natural Gas

Undiluted Propane

Pipe Size (in.)

Capacity in Cubic Feet of Gas per Hour

The following are gas line sizing examples from the

National Fuel Gas Code. Size your gas lines
properly, based on your installation, and all
applicable codes.