MagnaTherm Boilers and Water Heaters

Page 79

Code

Description

Lockout

or Hold

Procedure

187

Invalid DHW (Domestic Hot Water)
high limit enable setting

L

1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.

2. If fault repeats, verify electrical grounding.

3. If fault repeats, replace module.

188

Invalid DHW (Domestic Hot Water)
high limit response setting

L

1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.

2. If fault repeats, verify electrical grounding.

3. If fault repeats, replace module.

189

Invalid flame sensor type setting

L

1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.

2. If fault repeats, verify electrical grounding.

3. If fault repeats, replace module.

192

Invalid igniter on during setting

L

1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.

2. If fault repeats, verify electrical grounding.

3. If fault repeats, replace module.

193

Invalid ignite failure delay setting

L

1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.

2. If fault repeats, verify electrical grounding.

3. If fault repeats, replace module.

194

Invalid ignite failure response setting

L

1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.

2. If fault repeats, verify electrical grounding.

3. If fault repeats, replace module.\

195

Invalid ignite failure retries setting

L

1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.

2. If fault repeats, verify electrical grounding.

3. If fault repeats, replace module.

196

Invalid ignition source setting

L

1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.

2. If fault repeats, verify electrical grounding.

3. If fault repeats, replace module.

197

Invalid interlock open response setting

L

1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.

2. If fault repeats, verify electrical grounding.

3. If fault repeats, replace module.

198

Invalid interlock start check setting

L

1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.

2. If fault repeats, verify electrical grounding.

3. If fault repeats, replace module.

199

Invalid LCI (Limit Control Input) enable
setting

L

1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.

2. If fault repeats, verify electrical grounding.

3. If fault repeats, replace module.