Code

Description

Lockout

or Hold

Procedure

225

Invalid Flame threshold setting

L

1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.

2. If fault repeats, verify electrical grounding.

3. If fault repeats, replace module.

226

Invalid Outlet high limit setpoint setting

L

1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.

2. If fault repeats, verify electrical grounding.

3. If fault repeats, replace module.

227

Invalid DHW (Domestic Hot Water)
high limit setpoint setting

L

1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.

2. If fault repeats, verify electrical grounding.

3. If fault repeats, replace module.

228

Invalid Stack limit setpoint setting

L

1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.

2. If fault repeats, verify electrical grounding.

3. If fault repeats, replace module.

229

Invalid Modulation output setting

L

1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.

2. If fault repeats, verify electrical grounding.

3. If fault repeats, replace module.

230

Invalid CH (Central Heat) demand
source setting

L

1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.

2. If fault repeats, verify electrical grounding.

3. If fault repeats, replace module.

231

Invalid Delta T limit delay setting

L

1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.

2. If fault repeats, verify electrical grounding.

3. If fault repeats, replace module.

232

Invalid Pressure sensor type setting

L

1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.

2. If fault repeats, verify electrical grounding.

3. If fault repeats, replace module.

234

Invalid Outlet high limit enable setting

L

1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.

2. If fault repeats, verify electrical grounding.

3. If fault repeats, replace module.

235

Invalid Outlet connector type setting

L

1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.

2. If fault repeats, verify electrical grounding.

3. If fault repeats, replace module.

236

Invalid Inlet connector type setting

L

1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.

2. If fault repeats, verify electrical grounding.

3. If fault repeats, replace module.