Toa SX-2000 Series User Manual

Page 134

Advertising
background image

134

UTILITY

System Status Display Confirmation (SM unit screen)

2. Unit failure status

3. DC Power detail button

Clicking this button displays the DC power detail screen.

Displays the DC power and fuse status.
The "Normal" indication is displayed for normal conditions, the "Error" indication when irregularities are
detected, and the " – " indication when the failure check function is not in operation.
Clicking the [Close] button closes the DC power detail screen.

Displays the SX-2000SM's failure status.
Indicated items are DC power, SX link, Analog link and DS link.

Configuration

Displays the "Used" indication when the failure check function is in operation and the
"Unused" indication when the function is not in operation.

Status

Displays failure status.
Displays the "Normal" indication for normal conditions and the "Error" indication or the
cause of failure in the event of irregularities.
Displays the " – " indication when the failure check function is not in operation.

Display

System Status

Maintenance

Operating in maintenance mode.
• The SX-2000SM's DIP switch 2 is set to ON.
• CF card not inserted.

Initialization

Initialization in progress.

CPU off

The system is in the CPU off state.

Emergency cutoff

One of the SX-2000AO units is in the emergency mode that cuts off 24V DC to
allow emergency broadcasts to go through.

Error

The SX-2000SM has failed.

[Button indication priorities when multiple statuses occur simultaneously]

(High) Emergency cutoff

CPU off
CF card error, Maintenance
Error

(Low) Normal, Power failure (N), Emergency, Power failure (E), Initialization