Encrypted communications (xr500n/xr500e only), Programmer operation, Programmer lockout codes – DMP Electronics DMP Command Processor Panel XR500 User Manual

Page 11: Reset timeout

Advertising
background image

Digital Monitoring Products

XR500 Series Canadian Programming Guide

2

INTRODUCTION
1.3

Encrypted Communications (XR500N/XR500E only)

Some installations require secure data communications. DMP offers NIST approved AES encrypted

communication. Use a unique passphrase to enable encrypted communications and provide a secure

means for data communications. See Network Options.
An XR500E panel communicates using AES encryption. If you currently have an XR500N panel installed, you

may purchase a separate feature key to activate encrypted communications using the Feature Upgrade

process. Encrypted communication cannot be enabled on a standard XR500 panel. For more information

on the Feature Upgrade process see Section 21 in this document.

1.4

Programmer Operation

There are 21 programming sections to choose from:

Programming Item

Section in This Manual

Programming Item

Section in This Manual

Initialization

2

Output Information

12

Communication

3

Output Groups

13

Network Options

4

Menu Display

14

Messaging Setup

5

Status List

15

Device Setup

6

Printer Reports

16

Remote Options

7

PC Log Reports

17

System Reports

8

Area Information

18

System Options

9

Zone Information

19

Bell Options

10

Stop

20

Output Options

11

Set Lockout Code

21

Feature Upgrade

22

To choose a section for programming, press any top row Select key when the keypad displays the name of

that section. Sections 2 through 22 contain detailed instructions for each programming step.

1.5

Programmer Lockout Codes

The panel allows you to enter the programming function without entering a lockout code using steps

1 to 4 listed in Getting Started. We recommend, however, that you install a Lockout Code to restrict

programming to only those persons your company authorizes. You can do this by using the SET LOCKOUT

CODE feature in the Programmer. The Lockout Code restricts any unauthorized panel programming.
After resetting the panel and entering the code 6653, the keypad displays PROGRAMMER. Press COMMAND

to advance through the programming sections until SET LOCKOUT CODE displays (after STOP). Press any

top row Select key. The keypad displays ENTER CODE: – . Enter a 3 to 5 digit Programmer Lockout Code

and press COMMAND. The keypad displays ENTER AGAIN followed by ENTER CODE: –. Enter the same 3 to

5 digit code a second time and press COMMAND. The keypad displays CODE CHANGED.
Note: The panel does not accept a 5-digit Lockout Code higher than 65535.
Before accessing programmer functions enter the new code number. Write the Lockout Code number down

and keep it in a secure place with access limited to authorized persons only. Lost Lockout Codes require

the panel to be sent back to DMP for repair. You may cancel a Lockout Code by entering 00000 at the Set

Lockout Code command.

1.6

Reset Timeout

The panel has a feature that requires you to enter the Programmer within 30 minutes of resetting the

panel. After 30 minutes, if you attempt to program by entering the 6653 (PROG) code, the keypad

displays: RESET PANEL. You must reset the panel and enter the program code then begin programming

within the next 30 minutes.
If you are already in the Programmer and do not press any keys on the programming keypad for 30

minutes, the panel terminates programming. All data entered up to that time is Not saved unless you run

the Stop routine.
Note: Use the Stop routine to exit panel Programming. Ensure the keypad displays “SAVING PROGRAM” to

save all programming changes entered.

1.7

Power Up

When the XR500 Series Canadian panel is powered up after an AC power failure, any zone transitions are

not recognized for 60 seconds. Normal zone processing resumes at the end of the 60 seconds.