OUTPUT GROUPS

Output Groups

13.1

OUTPUT GROUPS

Output Groups

This function allows you to assign outputs to groups. Output groups can be assigned

to other areas of programming such as Output Options or Alarm Action of Zone

Information, just like single outputs are assigned. This allows the entire group of

outputs to turn on and off as required by the programming option.

13.2

GROUP NO: -

Group Number

Enter a group number from 1 to 20. Up to 20 different groups may be assigned.

13.3

GROUP NAME X X

Group Name

The group name displays. To change the default name, press any top row Select key

then enter up to 32 characters for the group name. Press COMMAND to enter the

outputs to be assigned to the group.

13.4

OUTPUT NO 1:

0

OUTPUT NO 2:

0

OUTPUT NO 4:

0

OUTPUT NO 5:

0

OUTPUT NO 3:

0

OUTPUT NO 7:

0

OUTPUT NO 8:

0

OUTPUT NO 6:

0

Output Number

Enter the Output number. Entry range is 1 to 6, 450 to 474, 480 to 499, 500 to 999

(outputs), D1 to D16 (doors), and G1 to G20 (groups). The maximum number of

outputs that can be assigned to a specific group is eight.
An output group may be assigned as one of the output numbers in another output

group.

Example: Output Group 1 consists of only four assigned outputs. Output Group

1 could be assigned as one output in Output Group 2. Output Group 2 could still

have 7 other outputs assigned to that group. When Output Group 2 is turned on, 11

outputs could be turned on. This allows Output Groups to be assigned within other

Output Groups providing many combinations.
Output groups 1 to 10 can be assigned by a user profile for applications such as

elevator control. See the XR500 User’s Guide (LT-0683CAN) Output Group section for

additional information.
Output groups 11 to 20 cannot be assigned to a profile and are available for

installation applications such as special lighting, etc. To assign these groups to a

profile, use Remote Link™ or System Link™ software from DMP.