Stop, 1  stop, Set lockout code – DMP Electronics DMP Command Processor Panel XR500 User Manual

Page 69: 1  set lockout code, 1 stop

Advertising
background image

Digital Monitoring Products

XR500 Series Canadian Programming Guide

60

ZONE INFORMATION
19.24

CRS ZONE NO YES

Cross Zone

Select YES to enable cross zoning for this zone. Cross zoning requires one or more armed

zones to fault within a programmed time before an alarm report is sent to the receiver.
When the first cross zoned zone trips, the cross zone time specified in System

Options begins to count down. When a second cross zoned zone trips or the first

zone trips a second time before the end of the count down, the bell action assigned

to the zone activates and the panel sends an alarm report for both zones.
If no other cross zoned zone trips before the cross zone time expires, the panel

sends only a zone fault report to the receiver.
Cross zoning is not compatible with all zone types: You can not enable cross zoning

for Fire verify zones or for any Fire zones that have Retard Delay enabled.

19.25

PRIORITY NO YES

Priority

Select YES to provide additional protection for the premises by requiring this zone to

be in a normal condition before its assigned area can be armed.

19.26

Fire Panel Slave Input

This option is available on Fire Zones (FI) only and allows a fire zone the ability to

provide slave communication operation for a separate fire alarm control panel. If

YES, this zone will transmit a restoral immediately when restored by the fire panel

being monitored. A sensor reset is not required to generate the restoral message.
If NO, this zone will operate as a standard fire type zone and a sensor reset is

required before the zone will return to normal. Default is NO.

19.27

Area Follower

Allows Night, Day, Aux 1, or Aux 2 burglary zones to be delayed by following any exit

or entry delay that is currently running in the area that is specified. Default is 0.

19.28

Zone Real-Time Status

Selecting YES allows Real-Time Status reports, such as Door Open or Closed with

zone number, to be sent using PC Log reporting. Selecting NO disables Real-Time

Status for this zone. Default is NO.

19.28.1

Door Number

If ZONE REAL-TIME STATUS is selected as YES, enter a door number (keypad bus

address) of 1-16. When a door number is selected, the door number is included

in the status report instead of the zone number. Enter 0 (zero) to disable this

feature and report the zone number. Default is 0 (no door).

19.29

ZONE AUDIT DAYS:

Zone Audit Days

Enter the number of days (0 to 365) allowed to elapse without the zone being tripped

before a fault message is sent. The message is sent to the receiver(s) programmed

to receive Supervisory/Trouble Reports at 10:00 am following the expiration of the

timer. Each time the zone is tripped, the Zone Audit Days timer restarts and begins

to countdown the number of days programmed. After the countdown expires, a fault

message is sent and the Zone Audit Days timer restarts and begins to countdown the

number of days programmed. Available for all zone types except fire and fire verify.

Enter 0 (zero) to disable this function. Default is 0 (zero).

19.30

Report with Account Number for Area

This option is only available for 24-hour zone types (Fire, Fire Verify, Panic,

Emergency, or Supervisory).
Enter the area number (1-32) to assign as a 24-hour zone type. This option sends

the account number of the programmed area with messages. If the entered area

number does not exist or is not valid, the account number programmed in the

Communication section is sent. Select 0 (zero) to have the report sent with the

account number programmed in Communication. Default is 0

FOLLOW AREA: 0

ZONE REAL-TIME

STATUS NO YES

FIRE PANEL SLAVE

INPUT: NO YES

DOOR NUMBER: 0

0

REPORT WITH ACCT

NO. FOR AREA: 0

SET LOCKOUT CODE