BELL OPTIONS

Bell Options

10.1

BELL OPTIONS

Bell Options

This section allows you to program the panel bell output functions.

10.2

BELL CUTOFF: 15

Bell Cutoff Time

Enter the maximum time from 1 to 99 minutes the Bell Output remains on. If the

area is disarmed, the cutoff time resets. Enter 0 (zero) to provide continuous bell

output. The default is 15 minutes.
Note: To support the Alarm Verify feature on an All/Perimeter or Home/Sleep/Away

system, set the Bell Cutoff Time to greater than 0.
Note: For SIA CP-01 False Alarm Reduction Installations, the Bell Cutoff Time must

be set to a minimum of six (6) minutes.

10.3

BELL TST NO YES

Automatic Bell Test

Select YES to turn on the Bell Output for 2 seconds each time the system

is

com pletely armed from a

keypad. This test is delayed until the Closing Wait

acknowledge is received (if programmed). If the Closing Wait acknowledge is not

received within 90 seconds, the bell test does not occur. Arming performed from an

Arming zone or from Remote Link™ does not activate the Bell Test.

10.4

BELL OUTPUT: 0

Bell Output

Enter the output number when needed to follow the panel Bell Output operation for

all action and off conditions. Enter 0 (zero) to disable.
Note: When BELL ACTION is set to T for Temporal Code 3, the Bell Output action for

an LX-Bus output is pulse.
Note: Bell Output should not be programmed for a Model 1135 Wireless Siren when

programmed in Output Information to Trip with Panel Bell.

10.5

BELL ACTION . . . . .

Bell Action

This section defines the type of Bell Output for zone alarms. Press COMMAND to

display the default Bell Output for each zone type. Press any Select key and enter

S for a Steady Bell Output, P for a Pulsed output, T for a Temporal Code 3 output,

and N for no Bell Output.
Note: Trouble conditions do not activate the Bell Output.

10.5.1

FIRE TYPE: P

Fire Bell Action

Defines Bell Action for Fire Type zones. The default is P.

10.5.2

BURGLARY TYPE: S

Burglary Bell Action

Defines Bell Action for Burglary Type zones and Exit Error output. The default is S.

10.5.3

SUPRVSRY TYPE: N

Supervisory Bell Action

Defines Bell Action for Supervisory Type zones. The default is N.

10.5.4

PANIC TYPE: N

Panic Bell Action

Defines Bell Action for Panic Type zones. The default is N.

10.5.5

EMERGNCY TYPE: N

Emergency Bell Action

Defines Bell Action for Emergency Type zones. The default is N.

10.5.6

AUXLRY 1 TYPE: N

Auxiliary 1 Bell Action

Defines Bell Action for Auxiliary 1 Type zones. The default is N.

10.5.7

AUXLRY 2 TYPE: N

Auxiliary 2 Bell Action

Defines Bell Action for Auxiliary 2 Type zones. The default is N.