15  bypass limit, 16  card plus pin (xr500e only), 17  house code – DMP Electronics DMP Command Processor Panel XR500 User Manual

Page 39: 18  detect wireless jamming, Bypass limit, Card plus pin (xr500e only), House code, Detect wireless jamming

Advertising
background image

Digital Monitoring Products

XR500 Series Canadian Programming Guide

30

SYSTEM OPTIONS
9.16

CARD PLUS PIN:

NO YES

Card Plus PIN (XR500E only)

Select YES to require all users to present a proximity credential and enter a PIN

number wherever user code entry is required for system functions accessed from a

keypad. Select NO to disable Card Plus PIN operation. Default is NO.

Note: The Card Plus PIN option is not designed to operate with All/Perimeter or

Home/Sleep/Away systems.
For an XR500E system using Card Plus PIN, two code entries are required by a user to

operate the system from a keypad. The first must be a code entered from a Wiegand

interface device (card, fob, etc.) using a reader such as the built-in reader of a DMP

Keypad. An external reader may also be used. The second code (User Pin) is keyed

in at the keypad or could be a second card or fob.
For a Card Plus PIN system, user codes (Card and PIN) are typically administered

using DMP System Link software.
When this option is first turned on at a keypad, the factory default (user number

9999, user code 99) must be available to enter the user menu at a keypad to then

add user codes and PIN numbers or to change existing users to add their PIN number.

If user 9999 was previously removed, re-enter this user and then set Card Plus

Pin = YES. Afterwards, user 9999 can be removed and the system only allows card

plus PIN entries.

Note: Current users of an existing system are immediately affected in that they must

have their user code information changed to add the user PIN.

9.17

WIRELESS

HOUSE CODE: 0

House Code

When using a DMP wireless system, enter a house code between 1 and 50. When

using FA Series wireless enter 99. See Wireless programming in Zone Information.

Default is 0 indicating no wireless system is being used.
The DMP house code identifies the panel, DMP receiver, and DMP transmitters to

each other. When operating, the DMP receiver listens for transmissions that have

the programmed house code and transmitter serial number.
Note: The flexibility of DMP two-way wireless operation allows an existing house

code to be changed in the panel at any time. The transmitters may take up to two

minutes to learn the new house code and continue operation.
Note: When any wireless zone programming is changed in the panel, wireless

receiver zone programming is updated. At that point, all wireless zones display as

normal for approximately 1 minute, regardless of the actual state of the zone.

9.18

DETECT WIRELESS

JAMMING: NO YES

Detect Wireless Jamming

This option displays when the House Code entered is for a DMP 1100 Series Wireless

system (1-50). When enabled and the wireless receiver detects jamming, a trouble

or alarm message displays in the Status List and is sent to the central station

receiver. Select YES to enable jamming messages to display in the Status List.

Select NO to disable jamming messages. Default is NO.

9.19

WLS AUDIBLE: DAY

WIRELESS AUDIBLE

ANY DAY MIN

Wireless Audible Annunciation

This option displays when the House Code entered is for a DMP 1100 Series Wireless

system (1-50). Press any top row key to select the keypad buzzer annunciation

method for wireless low battery and missing messages. Select ANY to enable

annunciation anytime. Select DAY to enable annunciation except during sleeping

hours (9 PM to 9 AM). Select MIN (minimum) to annunciate only Fire and Fire Verify

zones during daytime hours (9 AM to 9 PM). Default is DAY.

9.20

KEYPAD PANIC KEYS

ENABLED: NO YES

Enable Keypad Panic Keys

This option allows the two-button panic key operation selected at the keypad to

send the Panic, Emergency, or Fire message to the central station receiver. Select

YES to enable the two-button panic operation to operate. To disable the two-button

panic operation, select NO. Default is YES.

9.21

OCCUPIED

PREMISES: NO YES

Occupied Premises

For All/Perimeter or Home/Sleep/Away systems, select YES to allow the panel to

automatically disarm the interior area(s) when arming all areas and a perimeter

zone is not tripped during the exit delay. Select NO to disable this feature. Default

is YES.

Note: With a Home/Sleep/Away with Guest arming system, this feature only applies

to the main system.

Advertising