XR500 Series Canadian Programming Guide

18

DEVICE SETUP

• Door Schedules changes are allowed for devices that have a matching area(s)

as defined in Device Access Areas

• Door On/Off Menu operation is allowed for devices that have a matching area(s)

as defined in Device Access Areas

Note: The previous user actions also require the matching area(s) be programmed in

User Profile: Arm/Disarm area(s).
Status Display Allowed

When an area(s) is chosen, the following displays are allowed:

• Armed Status of the selected area(s)

• Zone Alarms and troubles for burglary (NT, DY, EX, A1, A2) type zones assigned to

the selected area(s)

• Late to Close status of the selected area(s)

• Zone Status (normal/fault) of zones that are assigned to the selected area(s)

Options and Actions Not Affected

The following options are not affected by the Display Areas operation. The User

Code authority level controls access to these items.

• Sensor Reset Menu

• Outputs On/Off Menu

• System Status Menu

• System Test/Panic Test • User Profiles

• Forgive Anti-Passback

• Service Request

• Set System Time and Date

• Fire Drill

• Display Events

• 24-hour zones display at keypads based on Status List programming only

Note: A common area and its operations cannot be assigned to a specific keypad.
Display Areas example: When Device 1 has Display Areas set to 20, 21, and 22, it

annunciates troubles and alarms only for zones assigned to those areas.

When arming/disarming from Device 1, only areas 20, 21, and 22 may be armed/

disarmed, even when the User Profile has authority to arm/disarm other system areas.
Exception: Disarming of other areas not selected in Display Areas can be

accomplished by presenting a card that has disarming authority and matching profile

areas with areas assigned in Device Access Areas.

6.9

STRIKE TIME:

5

Strike Time

This option displays if DOOR is selected as Device Type.

Enter a door access time, between 1 and 250 seconds, during which a keypad or access

control device relay is activated. Magnetic locks or electric door strikes are connected

to the relay and released for the length of the strike time. Default is 5 seconds.

Enter 0 (zero) to activate the device relay with a toggle action. This allows the user

to activate

or deactivate the device relay each time a valid user code is entered.

The device relay is activated

or deactivated until a user code is entered again.

Note: The Request to Exit door access time of a keypad or Model 733 Wiegand

Interface Module is not affected by this selection. It remains at 5 seconds.

6.10

STRIKE DELAY:

0

Strike Delay

This option displays if DOOR is selected as Device Type.

Enter the number of minutes, 0 to 9, to delay a door strike after a valid code is entered

or a card read occurs. When a valid code or card read or code is received, the activation

of the door strike is delayed for the number of minutes programmed. The standard door

strike message is sent to the Central Station receiver and logged in the Display Events at

the time of card read or code entry and is not delayed. During this delay, all subsequent

codes entered or cards presented to the reader for a door strike are ignored and no

record of the attempt is stored. Enter 0 (zero) to disable. Default is 0 (zero).

6.11

FIRE EXIT NO YES

Fire Exit Release

Select

YES to allow the door access relay at this address to be released whenever

Fire panic keys are pressed or a Fire or Fire Verify zone alarm is in the Status List.

The relay is reset whenever a Sensor Reset is performed to remove all Fire and Fire

Verify zone alarms from the Status List. Select

NO to not allow the door access relay

at this address to be released.

6.12

OUT GROUP NO YES

Output Group

Select

YES to allow the output group (relays) assigned to the user profile to turn ON

when the device relay is activated for the programmed strike time. This could be

used to operate an elevator control. Default is

NO. See the User Profiles section in

the Appendix of this document for more information about profiles.