3  supervision time, 4  led operation, 5  disarm/disable – DMP Electronics DMP Command Processor Panel XR500 User Manual

Page 61: 6  pir pulse count, 7  pir sensitivity, 3 supervision time, 4 led operation, 5 disarm/disable, 6 pir pulse count, 7 pir sensitivity

Advertising
background image

Digital Monitoring Products

XR500 Series Canadian Programming Guide

52

ZONE INFORMATION
19.9

NEXT ZN? NO YES

Next Zone

Select YES to terminate zone programming. The display returns to Zone Number,

allowing you to enter a new zone number. Select NO to make alter ations to the

Alarm Action for a zone. Alarm Action is defined beginning with section 16.12.
To program zones for wireless operation, select NO at the NEXT ZONE - NO YES

option. The WIRELESS NO YES option displays. If the zone you are programming

is intended for wireless devices, select YES. Select NO to continue programming

non-wireless zones in the 500 to 999 range.

• Zones 400 to 449 can be programmed for 1100 Series Key Fobs.
• Zones 500 to 699 can be programmed for FA Series Wireless.
• Zones 500 through 999 can be programmed for DMP 1100 Series Wireless.

DMP Wireless

For a DMP 1100X Wireless Receiver set the House Code from 1 to 50. See House Code programming

in System Options. Zones 500 through 999 can be programmed as Wireless zones. Set the XR500 Series

Canadian panel J23 jumper to X to enable on-board DMP Wireless operation. Briefly reset the panel using

the J16 jumper to activate Wireless operation. Refer to the XR500 Series Canadian Installation Guide

(LT-0681).
For an 1100 Series Key Fob see section 19.11.
For an FA Series Remote Wireless Receiver
see section 19.12.
NOTE: All wireless programming is stored in the XR500 Series Canadian panel. The 1100X Wireless

Receiver obtains the necessary programming information from the panel each time the receiver powers

up, when the programmer STOP routine is selected or the panel is reset. The receiver memory refresh

takes up to 10 seconds to complete depending on the number of wireless zones programmed and the Red

LED remains on during this time. Normal receiver operation is inhibited during the memory refresh period.

19.10

Wireless

Select YES to program this zone as a DMP wireless zone. You must program

the wireless House Code prior to adding DMP wireless zones to the system.

See House Code programming in System Options. Default is NO.

19.10.1

TRANSMITTER

SERIAL#: XXXXXXXX

Serial Number Entry

E

nter the eight-digit serial number found on the wireless device.

ALREADY IN USE

ZONE NUMBER: XXX

This message displays when the serial number is already programmed for

another zone. The programmed zone number displays.

19.10.2

TRANSMITTER

CONTACT:XXXXXXXX

Contact

This option displays if the serial number entered is for an 1101 or 1103 Universal

Transmitter or 1114 Wireless Four-Zone Expander. Press any top row key to

select the contact.

TRANSMTR CONTACT

INT EXT

This option displays when programming an 1101 or 1103 Transmitter. Select INT

to use the internal reed switch contacts. Select EXT to connect an external

device to the 1101 or 1103 terminal block. Default is INTERNAL.
By allowing both of the Model 1101 or 1103 transmitter contacts (INT and

EXT) to be used at the same time, two zones may be programmed from

one transmitter. When using both contacts, you must use consecutive zone

numbers. Zones 531 and 532 or zones 890 and 891 are acceptable zone

assignments.
For example, program transmitter serial number 01345678 as Zone 521 with

an INT contact type and Zone 522 with an EXT contact type. The same serial

number is used for both zones.

TRANSMTR CONTACT

1 2 3 4

This option displays when programming the 1114 Wireless Four-Zone Expander

with four input contacts. The same serial number is used for all four contacts.

Select the contact number to program. When using the contacts, you must use

ZONE INFORMATION

WIRELESS? NO YES

Advertising