XR500 Series Canadian Programming Guide

Digital Monitoring Products

27

SYSTEM OPTIONS

System Options

9.1

SYSTEM OPTIONS

System Options

This section allows you to select system-wide parameters.

9.2

SYSTEM:

AREA

System

This option allows you to program how the areas operate for arming and disarming.

The options you can choose are listed below:

AREA A/P H/A GST

AREA - All 32 areas can be programmed and operated independently.
ALL/PERIMETER - Area 1 is the Perimeter and Area 2 is the Interior.
HOME/SLEEP/AWAY - Area 1 is the Perimeter, Area 2 is the Interior, and Area 3 is the

Bedrooms. With the HOME/SLEEP/AWAY option, the user can:

1. Select HOME to arm just the perimeter.
2. Select SLEEP to arm the perimeter and interior (non bedroom areas).
3. Select AWAY to arm all three areas.
Note: A Home/Sleep/Away system can be configured to use all three areas or

only use the Home and Away areas.

HOME/SLEEP/AWAY WITH GUEST- This allows the alarm system to be divided into a

main house HOME/SLEEP/AWAY system and two other guest houses that also are set

up as HOME/SLEEP/AWAY systems.
Areas 1, 2, and 3 are the Perimeter, Interior, and Bedrooms for the Main house

system. Areas 4, 5, and 6 are the Perimeter, Interior, and Bedrooms for the Guest

1 house system. Areas 7, 8, and 9 are the Perimeter, Interior, and Bedrooms for

the Guest 2 house system. These areas are automatically assigned per system and

cannot be changed. See Display Areas in Device Setup to assign keypads to a system.

Zones are assigned to a system by assigning the system’s area numbers to the zone in

Zone Information programming.
When either All/Perimeter or Home/Sleep/Away is selected, the area names are

automatically assigned and cannot be modified.
Note: Areas 3-32 in an All/Perimeter system, areas 4-32 in a Home/Sleep/Away

system, and areas 10-32 in a Home/Sleep/Away with Guest system are not available

for use and are initialized.

9.3

INST ARM NO YES

Instant Arming

When YES is selected, the arming keypad displays INSTANT for selection during the exit

countdown delay when arming fewer than all areas of the system. At the time instant

arming is selected, any entry and exit delays programmed for the areas being armed

are ignored. The entry delay for previously armed areas is not affected by instant

arming. When NO is selected, INSTANT does not display during arming. Default is NO

for an Area System, and YES for an All/Perimeter or Home/Sleep/Away system.

9.4

CLS WAIT NO YES

Closing Wait

When YES is selected, the keypad displays ONE MOMENT... while waiting for

an acknowledgement from the receiver before arming the selected area(s) and

performing a Bell Test (if selected). Exit delays begin after the Closing Wait.

Opening/Closing reports must be YES to enable Closing Wait.

9.5

ENTRY DLY 2:

60

ENTRY DLY 3:

90

ENTRY DLY 1:

30

ENTRY DLY 4:

120

Entry Delay 1

Enter the Entry Delay time for all Exit type zones programmed to use Entry Delay 1.

When an armed Exit type zone is faulted, the keypad prewarn tone begins sounding.

All keypads programmed to prewarn for that zone display ENTER CODE:- and the

name of the zone causing the entry delay. When the first digit of a code is entered,

the prewarn tone stops at that keypad. If an invalid code is entered, the prewarn

tone begins sounding again. The area must be disarmed before the delay expires

or an alarm report is sent to the receiver and an alarm sounds. All zones in that

area are delayed along with the Exit zone. Entry Delay times can be from 30 to 250

seconds. Repeat the above for each entry delay being used in the system.
Note: Specific Exit Error operation is based on the Entry Delay used (1-4) with an EX

type zone. See Exit Delay.