DEVICE SETUP

734 Site Code Programming

6.18.9

Site Code Position

Enter the site code start position in the data string. Press any top row Select

key to enter a number between 1-255. Default is 1.

6.18.10

Site Code Length

Enter the number of characters the site code contains. Press any top row

Select key to enter a number between 1-16. Default is 8.

6.18.11

USER CODE

POSITION: 9

User Code Position

Define the User Code start bit position. Press any top row Select key to

enter a number between 0-255. Default is 9.

6.18.12

USER CODE

LENGTH: 16

User Code Length

Define the number of User Code bits. Press any top row Select key to enter

a custom number. Custom numbers can only be a number between 16-32.

On a 734N/734N-WiFi Module, custom numbers can be between 1-255.

The default is 16.

6.18.13

REQUIRE SITE

CODE?

NO YES

Require Site Code

Press the top row Select key under YES to use a site code.
In addition to User Code verification, door access is only granted when any one site

code programmed at the SITE CODE ENTRY option matches the site code received in

the Wiegand string.

6.18.13 .1

SITE CODE 1: -

Site Code Display

734 Module: You can program up to 8 three-digit site codes. Site code

range is 0-999. Any previously programmed site codes display. Dashes

represent blank site codes. Default is blank.

Note: A card with a site code greater than three digits cannot be used.

Use only cards with three-digit site codes.

734N/734N-WiFi Module: You can program up to 8 five-digit site codes. Site

code range is 1-65535. Any previously programmed site codes display. Site

Code 1 defaults to 127. Site Codes 2-8 default to blank. Dashes represent

blank site codes.

Site Code 1 displays first. Enter a site code number followed by the

Command key to advance to the next prompt, Site Code 2. To delete an

existing site code, press any Select key. Either enter a new site code

followed by Command, or press Command to leave blank and continue to

the next site code. Repeat these steps to change, delete, or add up to 8 site

codes

.

6.18.14

NO OF USER CODE

DIGITS: 5

Number of User Code Digits

The 734 module recognizes user codes from 4-10 digits in length. The 734N

/

734N-WiFi

module recognizes user codes from 1-10 digits in length.

Press any top row Select key

to enter a user code digit length between 4-10 digits. This number must match the

user code number length being used by the panel. Default is 5. For an XR500 Area

System, use 4 to 10 digits (typically 5). For all other systems and panels, use 4 digits.
Any selection above 5 digits require entry of the custom card definitions with custom

site and user code positions for the Wiegand string. When searching the bit string

for the user code, the digits are identified and read from left to right.

SITE CODE

POSITION: 1

SITE CODE

LENGTH: 8

SITE CODE 1:

(1-65,535) 127

0 1 1 1 0 1 0 1 1 0 1 1 0 1 0 1 0 0 0 1 1 0 0 1 1 1

First Bit

Received

Position = 0

Site Code

Position = 1

Length = 8

User Code

Position = 9

Length = 16

Last Bit

Received

Position = 25

In this example the Wiegand Code Length = 26 bits.