NETWORK OPTIONS

Network Options

(XR500N/XR500E only)

Network Options are provided to define the network configuration for the panel. This information will be

used during communication of messages via network or email.
Note: IP addresses and port numbers may need to be assigned by the network administrator. When

entering an IP, Gateway, or Subnet Mask address be sure to enter all 12 digits and leave out the periods.

For example, IP address 192.168.000.250 is entered as 192168000250.

4.1

DHCP

NO YES

DHCP Mode Enabled

If the panel uses a dynamic IP address select YES. When set to YES, the panel

operates using DHCP and does not use the Local IP Address number. When the DHCP

option is set to NO, the panel uses the IP address entered in Local IP Address. The

default value for DHCP mode is YES.

4.2

LOCAL IP ADDRESS

Local IP Address

192.168.0.250

Enter the local IP address. The Local IP Address must be unique and cannot be

duplicated. The default local IP address is 192.168.0.250.

4.3

GATEWAY ADDRESS

Gateway Address

192.168.0.1

Enter the local gateway address. The Gateway IP Address is needed to exit your

local network. The default gateway address is 192.168.0.1.

4.4

SUBNET MASK

Subnet Mask

255.255.255.000

Enter the local subnet mask assigned to the panel. The default subnet mask address

is 255.255.255.000.

4.5

DNS SERVER

DNS Server

192.168.0.1

Enter the IP address of the DNS (Domain Name System) used by the panel to resolve

domain names into IP addresses. The default address is 192.168.0.1.

4.6

PASSPHRASE
-

Passphrase

(XR500E only)

To enable encryption type an 8 to 16-character Passphrase using alphanumeric

characters. If you leave the Passphrase blank, the panel communicates with the

SCS-1R Receiver, but the data is not encrypted. The Passphrase is blank by default.
The XR500E panel is capable of communicating encrypted data to an SCS-101

Network Line Card installed at the receiver. The XR500E panel and the SCS-101 must

have the same secret password called a Passphrase.

Note: DO NOT LOSE THE PASSPHRASE. A lost or forgotten Passphrase requires that

the XR500E panel and every iCOM-E unit reporting in to the same iCOM-E unit at the

receiver be individually reprogrammed with a new passphrase.
Note: An XR500E panel communicates using AES encryption. If you currently have

an XR500N panel installed, you may purchase a separate feature key to activate

encrypted communications using the Feature Upgrade process described in the

Feature Upgrade Section. Encrypted communication cannot be enabled on a

standard XR500 panel.

4.7

734N LISTEN

734N Listen Port

PORT:

2002

Enter the port number that the 734N/734N-WiFi will use to send communication to

the panel. This must be the same port that is programmed in Panel IP Port within

the 734N Communication programming menu.

Note: The 734N Listen Port cannot be the same as the panel network programming

port.

4.8

734N PASSPHRASE

734N Passphrase

-

Enter an 8 to 16-character Passphrase to encrypt communication with the

734N/734N-WiFi module. The 734N Passphrase must match the 734N Passphrase

entered in Communication programming of the 734N. The Passphrase is blank by

default.
Note: A passphrase is required for operation.