15  report to transmit, 16  output number, 17  output action – DMP Electronics DMP Command Processor Panel XR500 User Manual

Page 66: Report to transmit, Output number, Output action

Advertising
background image

XR500 Series Canadian Programming Guide

Digital Monitoring Products

57

ZONE INFORMATION

FA Series Wireless

For an FA Series Remote Wireless Receiver set the House Code to 99. See House Code programming in

System Options. Only zones 500 to 699 can be programmed as FA Series Wireless zones for maximum of

200 Wireless Zones.
For a DMP 1100X Wireless Receiver see section 16.10.

19.12

ZONE INFORMATION

WIRELESS? NO YES

Wireless

Select YES to program a wireless zone connected to an FA Series FA400-DMP Remote

Wireless Receiver. Press the COMMAND key to continue with wireless programming.

19.12.1

CHECK IN TM:

60

Check-in Time

You can set wireless transmitters to check in automatically every 10, 30, or 60

seconds or not at all. To change the 60 second default, press any top row Select

key to display NONE 10 30 60. Select the check-in time you want for this zone.

Note: Refer to the Wireless Check-in and Supervision Time Definitions section

of the Appendix for supervision information.

19.12.2

INT CONT NO YES

Internal Contact

Select YES to use an internal contact on the wireless transmitter. Select NO

to use an external contact. When you select NO, the following two prompts

display.

19.12.3

EOL NO YES

End-of-Line

Select YES to supervise an external contact connected to the wireless

transmitter. At the contact, install a 2.2k Ohm End-of-Line resistor in parallel

for Normally Open contacts and in series for Normally Closed contacts.

19.12.4

NRM OPEN NO YES

Normally Open

Select NO if the contact connected to the wireless transmitter is Normally

Closed.

19.12.5

NEXT ZONE NO YES

Next Zone

Select YES to return to the ZONE NO: - prompt to program a new zone. Select

NO to display the Alarm Action option.

19.13

ALARM ACTION . . . .

Alarm Action

This option allows you to change any Zone Type standard definitions. When the Zone

Type is specified, the Alarm Action for that zone is stored in memory.
If the Zone Type is Blank, Night, Day, Exit, Auxiliary 1, or Auxiliary 2 it is a

non-24-hour zone and the Alarm Action programing begins with Disarmed Open.
If the Zone Type is Fire, Panic, Emergency, or Supervisory it is a 24-hour zone that is

always armed and the Alarm Action programming begins with Armed Open.
The Fire Verify Zone Type functions the same as Fire Type, with the following

exceptions: When a Fire Verify zone initiates an alarm, the panel performs a Sensor

Reset. If any Fire Verify zone initiates an alarm within 120 seconds after the

reset, an alarm is indicated. If an alarm is initiated after 120 seconds, the cycle is

repeated and a zone fault report is sent to the receiver.
Do NOT program Fire Verify Zone Types for Zone Retard.

19.14

DISARMED OPEN

Disarmed Open

Defines the action taken by the panel when the zone is opened while the area is

disarmed. There are three actions to define: Report to transmit, Relay Output to

activate, and Relay Output action.
You must also make these selections for the Disarmed Short, Armed Open, and Armed

Short zone conditions. Press COMMAND to continue.

Advertising