SYSTEM REPORTS

7.14.1

REMOTE CHANGE IP

Remote Change IP

This option displays when NET is selected for Send Local Changes. Enter the IP

address containing up to 12 digits. The Net IP Address must be unique and cannot

be duplicated on the network. Enter all 12 digits and leave out the periods. For

example, enter IP address 192.168.0.250 as 192168000250. The periods display

automatically. Default is 000.000.000.000

7.14.2

REMOTE CHANGE

Remote Change Port

This option displays when NET is selected for Send Local Changes. Enter the Port

number. Valid numbers are from 0 to 65535. Default is 2002.

7.14.3

Remote Telephone Number

This option displays when DD is selected for Send Local Changes. Press COMMAND to

enter the phone number the panel dials when sending programming changes. After

entering a phone number, the panel sends any panel changes to Remote Link.
The phone number can have two lines of 16 characters each to equal 32. Enter a

P to program a two second pause in the dialing sequence. The P character counts

as part of the 32 allowable characters. Enter *70P as the string first characters to

cancel call waiting. Dial tone detect is an automatic panel function.

System Reports

8.1

SYSTEM REPORTS

System Reports

Select specific system reports the panel sends to the receiver.

8.2

ABORT NO YES

Abort Report

YES allows the panel to send an alarm abort report to the receiver any time an area

is disarmed during Transmit Delay before an alarm report is sent and the Bell Cutoff

Time has not expired. After disarming an area, if any other area remains armed and

has zone(s) in alarm, the alarm abort report is not sent.
If the communication type is set to DD, a Warning: Alarm Bell Silenced report is also

sent if the alarm bell is silenced.
Note: Abort Reports are not sent for Fire, Fire Verify, or Supervisory type zones.

8.3

RESTORAL: YES

Restoral Reports

This option allows you to control when and if a zone restoral report is sent to the

central station receiver. Press any Select key to display the following options:

NO

YES

DISARM

NO - Disables the zone restoral report option. Zones continue to operate normally

but do not send restoral reports to the receiver.
YES - Enables the zone restoral report option. Zone restorals are sent whenever a

zone restores from a trouble or alarm condition.
DISARM - Causes the panel to send restoral reports for a non-24-hour zone whenever

a zone that has restored from a trouble or alarm condition is disarmed. All 24-hour

zones send restoral reports as they restore.

8.4

BYPASS

NO YES

Bypass Reports

YES allows the panel to send all zone bypasses, resets, and force arm reports to the

receiver. The bypass report includes the zone number, zone name, and the user

name and number of the individual operating the system. Reports are only sent if

O/C User in Communications is set YES for Receiver 1 or Receiver 2.

8.5

SCHD CHG NO YES

Schedule Change Reports

YES allows the panel to send all schedule changes to the receiver. The report

includes the day, opening time, closing time, extend schedule time, and the user

name and number of the individual making the change. Schedule changes made

through Remote Link™ are not sent to the printer or Display Events.