7  arming zone area assignment, 8  style, Arming zone area assignment – DMP Electronics DMP Command Processor Panel XR500 User Manual

Page 59: 8 style

Advertising
background image

Digital Monitoring Products

XR500 Series Canadian Programming Guide

50

ZONE INFORMATION
19.4

ZONE TYPE: BLANK

Zone Type

The Zone Type defines the panel response to the zone being opened or shorted.

This is called the Alarm Action. There are up to 13 possible alarm action responses

depending on the zone type and any restrictions it may have. See the Zone Type

chart in the Appendix.
When you assign a Zone Type to a zone, automatic zone responses are made. There

are 12 Zone Types to choose from. Application descriptions for each zone type can

be found in the Appendix of this manual.
To enter a new Zone Type, press any Select key. The display lists all of the available

Zone Types four at a time.

- -

NT DY EX

Blank, Night, Day, or Exit. Press COMMAND for additional zone types.

FI PN EM SV

Fire, Panic, Emergency, or Supervisory. Press COMMAND for additional zone types.

A1 A2 FV AR

Auxiliary 1, Auxiliary 2, Fire Verify, or Arming (keyswitch). Press COMMAND for

additional zone types.
If you select Blank, Night, Day, Exit, Auxiliary 1, Auxiliary 2, or Arming as the Zone

Type, the zone must be assigned to an active area. If you select Fire, Fire Verify,

Panic, Emergency, or Supervisory as the Zone Type, it is a 24-hour zone that is always

armed and no area assignment is needed.
Zone Type Specifications

The panel contains 12 default zone types for use in configuring the system. These zone

types provide the most commonly selected functions for their applications. All zone

types except the Arming zone type can be customized by changing the options listed

below. Arming zone type programming continues at Arming Zone Area Assignment.
Refer to the Appendix for complete zone type descriptions.

19.5

AREA NO: -

Area Assignment

Enter the area number where the Night, Day, Exit, Auxiliary 1, or Auxiliary 2 zone

is being assigned. For an Area system, area numbers 1-32 can be assigned. For a

Home/Sleep/Away with Guest system, area numbers 1-9 can be assigned.

AREA: PERIMETER

In an All/Perimeter or Home/Sleep/Away system, the currently selected area,

Perimeter, Interior, Bedroom displays.

INT

PERIM

On an All/Perimeter system, select INT to program zones for the interior area and

select PERIM to program zones for the perimeter area.

INT

BDRM PERIM

On a Home/Sleep/Away system, select INT to program zones for the interior area,

select BDRM to program zones for the bedroom area, and select PERIM to program

zones for the perimeter area.

19.6

FIRE BELL OUT:

0

Fire Bell Output

This output (1 to 6, 500 to 999, G1 to G20, or D1 to D16) is turned on any time a

Fire, Fire Verify, or Supervisory zone is placed in alarm. The output is turned off by

any the following actions:

• When the User Menu Alarm Silence function is performed.
• When a valid user code is entered to silence the bell.
• When the Silence key is pressed on the 630F Remote Fire Command Center.
• Using the Outputs On/Off function in the User Menu.
• The expiration of the Bell Cutoff time.

This output can be connected to a lamp, LED, or buzzer using the DMP Model 716

Output Expansion Module.

19.7

ARM/DIS AREAS

Arming Zone Area Assignment

In an Area or Home/Sleep/Away with Guest system, if the zone has been

programmed as an Arming Type (AR), enter the areas that the zone controls.

Advertising