Warning – Dunkirk Q90-200 Series II User Manual

Page 13

Advertising
background image

13

5 - WATER CHEMISTRY AND GENERAL ANTIFREEZE GUIDELINES

Boiler Water Quality and Antifreeze

Water treatment and antifreeze protection must be applied

to all aluminum series high efficiency gas-fired boilers

using antifreeze protection.
Clean System First

• Before connecting boiler to heating system, clean

and flush system thoroughly. Verify system is free of

sediment, flux and residual boiler water additives.

• Systems having antifreeze not recommended must be

completely flushed to ensure no old antifreeze remains.

In older systems obviously discolored, murky or dirty

water; or pH reading outside acceptable range (between

7.0 and 8.0) are indications system should be cleaned

or treated. Thoroughly flush system with clean water to

remove sediment or contaminants. Sludge and iron oxide

deposits can cause rapid breakdown of inhibitors.

• Flush with clean water. If chemical cleaners are used,

use only those recommended for use with aluminum

boilers. Follow chemical cleaner manufacturer’s

instructions completely.

• DO NOT mix different manufacturer’s products.

Fill Water and Chemistry

Verify water used to fill system meets these requirements:

• System fluid pH maintained between 7.0 and 8.0.

• Maintain water hardness below 7 grains hardness.

• Filling with chlorinated potable water is acceptable. DO

NOT fill boiler with water containing chlorine in excess

of 100 ppm.

• DO NOT use inhibitors or other additives that are not listed.

• Consult local water treatment specialist for

recommendations if any of above requirements is

outside stated ranges.

Eliminate System Leaks

• Continuous addition of make-up water will constantly

add oxygen to system. Eliminate all system leaks. All

system leaks must be repaired immediately.

• Verify expansion tank is operational and properly sized.

Undersized expansion tanks cause relief valve weeping

and substantial make-up water addition.

• Operation of this boiler in a system containing

significant amounts of dissolved oxygen can cause

severe heat exchanger corrosion damage.

• This boiler is not designed for use in systems

containing regular additions of make-up water. Regular

additions of make-up water may cause severe heat

exchanger damage. System leaks may not always be

visible. Unseen system leak will become obvious if boiler

pressure decreases when make-up valve is closed.

• This boiler is designed for closed loop hydronic heat

system only.

Boiler is not suitable for natural gravity

type installations, or any other open type system.

General Guidelines When Using Antifreeze

• Use only antifreeze products recommended for use with

aluminum boilers. See Table 5 page 14.

• Continuous addition of make-up water will dilute power

of antifreeze and change buffers ability to maintain pH.

• Flush old antifreeze from system. Flush boiler and

system separately.

• Do not use antifreeze unless required.

• Antifreeze must be of type as listed in this manual due

to their operational characteristics of : type 356 T6

aluminum at operating temperatures between 20°F

(-6.7°C) and 250°F (121°C).

• Always clean system prior to using antifreeze.

• Follow antifreeze manufacturer’s instructions for

use, safe handling and storage. Refer to MSDS

(Material Safety Data Sheets) provided by antifreeze

manufacturer for potential hazards and first aid

procedures for exposure or ingestion.

• Antifreeze will raise pH of hydronic solution in heating

system above recommended level due to corrosion

inhibitors. Solution must be treated to maintain

pH within recommended level. Follow antifreeze

manufacturer’s instructions to adjust pH.

• If system leaked, adjust water and antifreeze

chemistry. To avoid damage to boiler, check pH

and chemistry of boiler solution. Consult antifreeze

manufacturer for recommendations.

• Take pH reading annually, and adjust as necessary.

Follow antifreeze/inhibitor manufacturer’s instructions

for details on how to adjust pH.

• Antifreeze solutions can break down over time.

Failure to check antifreeze chemistry on annual basis

may result in accelerated corrosion of boiler and

other system components. Consult with antifreeze

manufacturer for recommendations.

• Use of antifreeze in any boiler will reduce heating

capacity as much as 10-20%. Take into consideration

when sizing heating system, pumps and expansion

tank. Consult antifreeze manufacturer’s literature for

specific information on reduced capacity.

• Using antifreeze manufacturer’s instructions, determine

freezing temperature needed and use correct amount

of antifreeze. Never exceed 50% antifreeze by volume.

• Boiler operating pressure must remain below 15 psi

for antifreeze solutions that specify maximum of

250°F (121°C). Otherwise, increase system operating/

tank pressure to 20 psig. Refer to expansion tank

manufacturer instructions for adjusting tank

pressure.

WARNING

Fire, explosion, asphyxiation hazard. Inadequate

dielectric isolation, incorrect water treatment or

antifreeze application may cause damage to boilers

heat exchanger. Improper installation could result

in death or serious injury. Follow these instructions

completely.

!

Advertising