Dunkirk Q90-200 Series II User Manual

Page 35

Advertising
background image

35

System Status
Indicator lights track operating sequence. If system locks out, lights indicate point in sequence of operation were lockout

occurs. Refer to following pages for detailed troubleshooting procedures.

LIGHT

STATUS

INDICATES

POWER

ON

IBC is energized through 24 volt transformer.

OFF

IBC is not energized.

Blinking

IBC receives more than 40 VAC.

PURGE

ON

IBC is energizing draft inducer and air flow is proven.

OFF

Off during purge cycle - draft inducer is not powered on or air flow is not proven.

Off during igniter and run cycle - normal operation, purge cycle complete.

Blinking

IBC is locked out. Problem could indicate false positive proof of air flow. Blocked vent,

intake air pipe, flue way, or orifice in negative pressure hose.

IGNITER

ON

IBC is energizing igniter.

OFF

Igniter is not energized.

VALVE

ON

IBC is energizing gas control valve to open.

OFF

Gas control valve is closed.

Blinking

IBC is locked out. Problem is flame has not been proven in three (3) ignition attempts.

May be due to broken igniter or lack of/low flame signal, or no gas.

FLAME

On Bright

Flame proven.

On Dim

Checking for flame signal (during trial for ignition)

OFF

Flame unproven.

13 - SEQUENCE OF OPERATION DIAGNOSTICS