Table 1 - SEA LEVEL RATINGS (NATURAL AND PROPANE GASES)

Model

Input

(MBH)

(1)

Heating Capacity

(MBH)

(1)(2)

Net AHRI Rating

(MBH)

(1)

Shipping Weight

(lbs.)

AFUE

(2)

125

125

113

98

284

90.0

150

150

134

117

284

90.0

175

175

158

137

284

90.0

200

200

180

157

284

90.0

(1)

1 MBH = 1,000 Btuh (British Thermal Units Per Hour)

(2)

AFUE (Annual Fuel Utilization Efficiency) and Heating Capacity is based on Department of Energy test procedure.

1 -BOILER RATINGS & CAPACITIES

Figure 1 - Boiler Jackets

These low pressure gas-fired hot water boilers are design certified by CSA International, for use with natural and propane

gases.
Boilers are constructed and hydrostatically tested for maximum working pressure of 50 psi (pounds per square inch)

in accordance with A.S.M.E. (American Society of Mechanical Engineers) Boiler and Pressure Vessel Code, Section IV

Standards for heating boilers.
Boilers are certified in accordance with ANSI (American National Standards Institute) Z21.13 standards as gas-fired, direct

vent, condensing, hot water boilers.
Heating Capacity indicates amount of heat available after subtracting losses up the stack. Most of this heat is available

to heat water. Small portion is heat loss from jacket and surfaces of boiler, it is assumed this heat stays in the structure.

Net AHRI Rating represents portion of remaining heat applied to heat radiation or terminal units (i.e. Finned tube

baseboard, cast iron radiators, radiant floor, etc.). Difference between Heating Capacity and Net AHRI Rating, called piping

and pickup allowance, establishes reserve for heating volume of water in the system and offsetting heat losses from

piping. Net AHRI Ratings shown are based on piping and pickup factor of 1.15. Net AHRI Rating of boiler selected should

be greater than or equal to calculated peak heating load (heat loss) for building or area(s) served by boiler and associated

hot water heating systems. Manufacturer should be consulted before selecting boiler for installations having unusual

piping and pickup requirements.