Boiler is equipped for residential installations. If used for

commercial applications; additional code requirements

must be adhered to. This may require additional controls,

including but not limited to manual reset low water cut off,

manual reset high temperature limit, and wiring and/or

piping modifications.

1.

Installation must conform to the requirements of the

authority having jurisdiction or, in the absence of such

requirements, to the National Fuel Gas Code, ANSI

Z223.1/NFPA 54 and/or Natural Gas and Propane

Installation Code, CAN/CSA B149.1.

2.

Where required by authority having jurisdiction,

installation must conform to the Standard for Controls

and Safety Devices for Automatically fired Boilers,

ANSI/ASME CSD-1.

3.

Be certain gas input rate is correct. Over-firing may

result in early failure of boiler components; this may

cause dangerous operation. Under-firing may result in

too much air for pre-mix burner causing poor or loss of

combustion.

4.

Never vent products of combustion from this boiler to

enclosed space. Always vent to outdoors. Never vent to

another room or to inside building.

5.

Verify adequate outdoor air supply to boiler for

complete combustion.

6.

Follow regular service and maintenance schedule for

efficient and safe operation.

7.

Keep boiler area clean of debris and free from

combustible materials, gasoline and other flammable

vapors and liquids.

8.

Proper through-the-wall or through-the-roof

combustion venting shall be in accordance with

materials and methods described in this manual.

Installation must comply with local codes.

9.

Boiler and related hot water heating systems are

not do-it-yourself items. Installation and service by

qualified professionals are required.

2 - SAFE INSTALLATION AND OPERATION

Installers - Follow local regulations with respect to

installation of CO (Carbon Monoxide) Detectors. Follow

maintenance recommendations in this manual. See

“Maintenance And Cleaning” on page 48.

Boiler Sizing

• Verify you have selected the boiler with proper capacity

before continuing installation. AHRI Rating of boiler

selected should be greater than or equal to calculated

peak heating load (heat loss) for building or area(s) served

by boiler and associated hot water heating systems. See

“Boiler Ratings & Capacities” on page 3.

• Heat loss calculations should be based on approved

industry methods.

Considerations For Boiler Location

Before selecting boiler location, consider following.

• Supplied with correct type of gas (natural gas or

propane).

• Connected to suitable combustion air intake piping

system to supply correct amount of fresh (outdoor) air

for combustion. See “Combustion Air And Vent Pipe” on

page 15.

• Connected to suitable venting system to remove

hazardous products of gas combustion. See “Combustion

Air And Vent Pipe” on page 15.

• Connected to suitable hot water heating system.
• Supplied with suitable electrical supply for all boiler

motors and controls.

• Connected to properly located thermostat or operating

control. (Not included with boiler)

WARNING

Fire hazard. Do not install boiler on carpeting.

Failure to follow these instructions could result in

death or serious injury.

!

• Placed on level surface (DO NOT install on carpeting)
• Condensate drain line must be pitched down to floor

drain or external condensate pump with reservoir at ¼”

per foot (21 mm/m) (wood frame or blocks may be used

to raise boiler).

WARNING

Improper installation, adjustment, alteration, service

or maintenance could result in death or serious

injury.

!