15 - troubleshooting, Troubleshooting chart 6 – Dunkirk Q90-200 Series II User Manual

Page 46

Advertising
background image

46

Troubleshooting Chart 6

RUNS FOR 25-50 SECONDS,

THEN TURNS OFF.

CHECK FIRING RATE OF UNIT.

IS UNIT FIRING AT THE CORRECT RATE?

NO

DOES THE UNIT USE LP GAS.

YES

NO

CHECK GAS ORFICICE SIZE.

IS GAS ORIFICE SIZE CORRECT.

CHECK REPAIR PARTS LIST

FOR CORRECT SIZE. IS GAS ORIFICE

CLEAR OF BLOCKAGE.

ADJUST RATE AS DESCRIBED IN THE

CHECK OUT PROCEDURE AND

ADJUSTMENT SECTION

OF THE MANUAL.

CHART 5

NO #2

YES

CHECK BURNER FOR ANY DETERIORATION

IN THE FLAME PORTS. ARE BURNER PORTS

IN GOOD CONDITION.

NO

REPLACE WITH CORRECT

AIR BAFFLE.

YES

CHECK FLAME SIGNAL > 0.6uA?

CONSULT BOILER MFGR. FOR

SPECIFIC INSTRUCTIONS. REQUIRES

SPECIFIC TOOLS.

NO

YES

REPLACE BURNER

REPLACE IBC

BOILER SHUTS OFF BEFORE END OF

CALL FOR HEAT. ARE HI LIMIT

AQUASTAT CONTACTS CLOSED?

NO

BOILER OFF ON HIGH LIMIT. IS

ACTUAL BOILER WATER TEMP.

GREATER THAN HI LIMIT SET POINT

MINUS 30°F CONTROL DIFFERENTIAL?

NO

NO

REPLACE

AQUASTAT

OK

YES

SEE TROUBLESHOOTING PATH

#2 ABOVE

CHART 5

NO #3

CHART 5

YES

SET THERMOSTAT BELOW ROOM

TEMPERATURE TO END CALL FOR

HEAT

DOES CIRCULATOR PUMP STOP?

NO

ARE THERMOSTAT CONTACTS OPEN?

REPLACE THERMOSTAT

NO

YES

REPLACE IBC

YES

VALE LIGHT IS OFF

REMOVE WIRING HARNESS

CONNECTION CN9 FROM GAS

CONTROL DOES GAS CONTROL

CLOSE?

NO

REPLACE GAS CONTROL

NO

YES

YES

DOES DRAFT BLOWER

STOP AFTER 30

SECOND POST PURGE?

NO

REPLACE IBC

YES

YES

SYSTEM OK

YES

REPLACE GAS CONTROL.

15 - TROUBLESHOOTING