WARNING

Electrical shock hazard. Turn OFF electrical power

supply at service panel before making electrical

connections. Failure to do so could result in death

or serious injury.

!

NOTICE

Use copper conductors only.

Electrically bond boiler to ground in accordance with

requirements of authority having jurisdiction. Refer to

National Electrical Code, ANSI/NFPA 70.

Electric Power Supply
Turn OFF electrical power supply at service panel and boiler

before making electrical connections.

• Run 120 volt circuit from separate over current protection

device in electrical service entrance panel, 15 ampere

circuit.

• Service switch is pre-wired and located on exterior boiler

jacket. See Figure 15 for location of service switch,

junction box, and power supply connection points.

• Connect black (hot) lead from power supply to either of

unused brass screws on service switch.

• Connect white (neutral) lead from power supply to white

screw on service switch.

• Connect green (ground) lead from power supply to

ground (green) screw on service switch.

• Receptacle on service switch is powered regardless of

whether switch is on or off, and could be used as power

supply for external condensate pump if one is used.

• Run 14 gauge or heavier copper wire from boiler to

grounded connection in service panel or properly driven

and electrically grounded ground rod.

9 - ELECTRICAL WIRING

Figure 16 - Field Wiring Connection