11 - STARTUP

If Burner Appears To Pulsate During Ignition:

1.

Turn off boiler power. Shut off gas supply to boiler.

2.

Take burner assembly apart by removing combustion

air blower and gas valve/venturi assembly from boiler.

Visually inspect inside of burner. Look for debris (PVC

shavings, etc.). Remove debris if present.

3.

Reassemble burner assembly, turn gas supply and

boiler power back on, relight boiler.

If Burner Continues To Pulsates Or Fails To Light:

1.

Check for proper vent, intake pipe sizing, proper

vent lengths and vent configuration. Refer to “Safe

Installation And Operation” on page 6 and “Combustion

Air/ Vent Requirements” on page 16.

2.

Check for proper gas supply pressure and proper gas

line sizing to boiler. Refer to “Check Gas Supply” on

page 22.

3.

Check for orifice in negative pressure hose at gas

valve, and 2” air intake pipe upstream of gas valve.

4.

Relight boiler.

5.

If boiler still does not light,

A. Disconnect air inlet pipe. Allow boiler to start, verify

boiler firing rate and combustion properties.

B. Disconnect inlet air pipe by removing PVC inlet

air piping from coupler located on air inlet of gas

valve/venturi assembly.

C. Relight boiler.

6.

Verify firing rate and combustion when boiler lights.

Refer to “Adjustments And Checkout” on page 35. If air

inlet piping was disconnected in step 4 (above), leave it

disconnected and make first adjustment. Reconnect air

inlet piping, then verify combustion CO

2

, adjust again if

necessary.

7.

If burner pulsation continues or boiler fails to light after

performing above procedures, contact technical service

for assistance.