Differential air pressure switch is safety device which

prevents boiler from firing if there is air intake, boiler heat

exchanger or vent blockage.

Following steps and diagram indicate location of connection

points required to measure offset pressure using inclined

Manometer or Differential pressure gauge. Only one device

is required to measure offset pressure.

1.

Turn off service switch, or lower thermostat setting.

2.

Remove vinyl caps from Tee.

3.

Install testing lines as shown to inclined manometer or

differential pressure gauge with ability to read 0.01” to

at least 6.0” w.c.

4.

Turn on service switch and set thermostat to call for

heat.

5.

If manometer readings do not correspond to Table 11

check for possible causes:

• Blockage or moisture in suction lines to switch.
• Blockage or moisture in orifice installed in suction

lines to switch.

• Blockage in air intake or vent pipes.
• Undersized air intake or vent pipes.
• Loose blower wheel on motor shaft.
• Incorrect pressure switch or pressure switch set-

point.

• Gas valve out of adjustment.

6.

When pressure reading corresponds to Table 11

and pressure switch is operating properly, remove

testing lines and reinstall vinyl caps to tee and 3-way

connector.

Table 11 - Correct Manometer Readings

Boiler Status

Differential Pressure

Switch Contacts

Not Running

0”

3.5”

Closed

0.5”

Open

Running

Without

Blockage

(Approximate

minimum vent

lengths)

1.00” for Model 125

3.5”

0.5”

Closed

Closed

1.50” for Model 150

1.50” for Model 175

2.00” for Model 200

Running With

Blockage

Greater Than or Equal

To Setpoints

3.5”

Open

0.5”

Closed

Figure 22 - Locations Of Connection Points

Required To Check Differential Air

Pressure

Differential Air Pressure Switch Check

15 - TROUBLESHOOTING